During a utility power failure, the rectifier no longer has an AC utility source from which to 
supply the DC output current required to support the inverter. The input contactor K1 opens and 
the battery instantaneously supplies energy to the battery converter. The converter either bucks 
or boosts the voltage so that the inverter can support the customer’s load without interruption. 
If bypass is common with the rectifier input, the backfeed protection contactor K5 also opens. 
The opening of contactors K1 and K5 prevent system voltages from bleeding backwards 
through the static switch and rectifier snubber components and re-entering the input source. 
If the input power fails to return or is not within the acceptance windows required for normal 
operation, the battery continues discharging until a DC voltage level is reached where the 
inverter output can no longer support the connected loads. When this event occurs, the UPS 
issues another set of audible and visual alarms indicating SHUTDOWN IMMINENT. Unless the 
rectifier has a valid AC input soon, the output can be supported for only two minutes before the 
output of the system shuts down. If the bypass source is available, the UPS transfers to bypass 
instead of shutting down. 
If at any time during the battery discharge the input power becomes available again, contactors 
K1 and K5 close and the rectifier begins to supply DC current to the converter and inverter. At 
this point, the unit returns to normal mode. Depending on the total load and the duration of the 
battery discharge, battery current limit alarms may be seen for a short time due to the current 
required to recharge the battery.
4.3 UPS system one line configurations
One line drawing
UPS model
Voltage
System type
Input
Output
Figure 4-5
9395-275/225
400
400
Single module – Reverse transfer 
dual-feed
Figure 4-6
9395-275/275
400
400
Single module – reverse transfer 
dual-feed with typical maintenance 
bypass panel