5-4
Section
P: Set Network Parameters
83
5-4
P: Set Network Parameters
“P: Set Network parameters” is used to modify network communications param-
eters to provide the most suitable Controller Link communications for the user
application.
Note
1) Network parameters cannot be set during data link operation. Set the net-
work parameters after stopping the data links. (See 5-3-13 Starting and
Stopping Data Links 
on page 77.)
2) The same network parameters are used for all nodes within the Controller
Link Network. Therefore, any change in each network parameters will affect
all nodes within the network.
3) Before executing “P: Set Network parameters”, always set pin 1 of the DIP
switch on the CS1-series and CQM1H-series CPU Unit to OFF.
4) Before executing “P: Set Network parameters”, always set the system pro-
tect key switch on the CVM1 or CV-series CPU Unit to NORMAL.
1, 2, 3...
1. Select “P: Set Network parameters” from the Main Menu.
2. Specify the address of the Controller Link Network for which network param-
eters are to be changed. Enter the network address with Numeric Keys, then
press the Enter Key. The current network parameter settings for the speci-
fied network will be displayed.