Omron FQM1-CM001 ユーザーズマニュアル

ページ / 414
177
Pulse Outputs
Section 7-6
Set the pulse output operation mode to 1 shot in advance in the System
Setup, as shown in the following table.
Note
A pulse output port that is being used for one-shot pulse outputs cannot be
used for any other pulse output functions. 
The elapsed time of the one-shot pulse output is stored in 8-digit hexadecimal
in words A621 and A620 (pulse output 1) or A623 and A622 (pulse output 2).
When the one-shot pulse output is turned ON, the content of the correspond-
ing words is set to 0000 0000 hex and the content is incremented as time
passes. The final value is retained when the one-shot output is turned OFF. 
One-shot Pulse Output Specifications
Tab page
Function
Setting
Pulse Output
Pulse Output 1 
− Operation mode
1 shot (one-shot pulse output)
Pulse Output 2 
− Operation mode
1 shot (one-shot pulse output)
ON 
OFF
One-shot pulse output 
Turned ON by STIM
instruction execution.
Turned OFF by hardware. 
Setting units: Select 0.01 ms, 0.1 ms, or 1 ms.
Setting range: 0001 to 270F Hex (1 to 9,999)
Word
Bits
Function
Contents
A620
00 to 15
Elapsed time 
of One-shot 
pulse output 1
Lower 
4 digits
Contains the elapsed time of the 
one-shot pulse output in 8-digit hexa-
decimal.
The content can range from 0000 0000 
to 0000 270F hex, and the units are set 
to 0.01 ms, 0.1 ms, or 1 ms with the 
STIM(980) instruction.
Note These words are refreshed dur-
ing the Motion Control Module’s 
I/O refreshing.
A621
00 to 15
Upper 
4 digits
A622
00 to 15
Elapsed time 
of One-shot 
pulse output 2
Lower 
4 digits
These words function just like the 
words for pulse output 1, described 
above.
A623
00 to 15
Upper 
4 digits
Item
Specification
Pulse ON time
0.01 to 9,999 ms (Can be set with the STIM(980) instruction.)
Operating conditions 1. Set the pulse output operation mode to 1 shot in the System 
Setup.
2. Execute the STIM(980) instruction with operand C1 = #0001 
or #0002.
Response time
Response time when the STIM(980) instruction is executed at 
the beginning of an interrupt task:
0.2 ms max. from the generation of the interrupt until the 
one-shot pulse output goes ON