Omron FQM1-CM001 ユーザーズマニュアル

ページ / 414
218
Analog Input Functions
Section 7-9
7-9-4
Related Areas and Settings
System Setup
Tab page
Function
Settings
Time when setting 
becomes effective
Analog Input/
Output
Both inputs 
and outputs
Input 
method
0 hex:
END refresh
1 hex:
Immediate refresh (Refresh with PRV(881).)
At power ON and 
start of operation
Output 
method
0 hex:
END refresh
(Content of A560 and A561 is output as 
analog output after execution of END 
instruction.)
1 hex:
Immediate refresh
(Analog output when SPED(885) or 
ACC(888) is executed. A560 and A561 
used for monitoring.)
At power ON and 
start of operation
Inputs
Input range
00 hex:
−10 to 10 V
01 hex: 0 to 10 V
02 hex: 1 to 5 V (4 to 20 mA)
03 hex: 0 to 5 V
At power ON
Outputs
Output 
range
00 hex:
−10 to 10 V
01 hex: 0 to 10 V
02 hex: 1 to 5 V
03 hex: 0 to 5 V
5A hex: Disable outputs (See note.)
Note Outputs can be disabled to shorten the I/O 
refreshing time or reduce the Motion Control 
Module’s power consumption.
At power ON
Output stop 
function
0 hex:
Clear outputs
1 hex:
Hold outputs
2 hex:
Maximum value
Outputs
Output 
range
These parameters have the same settings as output 
1, above.
Output stop 
function