Inspections
Section 10-1
10-1 Inspections
Daily or periodic inspections are required in order to maintain the FQM1 in
peak operating condition.
10-1-1 Inspection Points
Although the major components in the FQM1 have an extremely long life time,
they can deteriorate under improper environmental conditions. Periodic
inspections are thus required to ensure that the required condition is being
maintained. 
Inspection is recommended at least once every six months to a year, but more
frequent inspections will be necessary in adverse environments.
Take immediate steps to correct the situation if any of the conditions in the fol-
lowing table are not met.
Inspection Points for Periodic Inspections
No.
Item
Inspection
Criteria
Action
1
Source Power 
Supply
Check for voltage fluctuations 
at the power supply terminals.
The voltage must be within 
the allowable voltage fluctu-
ation range.
(See note.)
Use a voltage tester to check the 
power supply at the terminals. Take 
necessary steps to bring voltage 
fluctuations within limits.
2
I/O Power Sup-
ply
Check for voltage fluctuations 
at the I/O terminals.
Voltages must be within 
specifications for each 
Module.
Use a voltage tester to check the 
power supply at the terminals. Take 
necessary steps to bring voltage 
fluctuations within limits.
3
Ambient environ-
ment
Check the ambient tempera-
ture. (Inside the control panel 
if the FQM1 is in a control 
panel.)
0 to 55
°C
Use a thermometer to check the 
temperature and ensure that the 
ambient temperature remains 
within the allowed range of 0 to 
55
°C.
Check the ambient humidity. 
(Inside the control panel if the 
FQM1 is in a control panel.)
Relative humidity must be 
10% to 90% with no con-
densation.
Use a hygrometer to check the 
humidity and ensure that the ambi-
ent humidity remains within the 
allowed range.
In particular, verify that there is no 
condensation or icing caused by 
sudden temperature changes.
Check that the FQM1 is not in 
direct sunlight.
Not in direct sunlight
Protect the FQM1 if necessary.
Check for accumulation of 
dirt, dust, salt, metal filings, 
etc.
No accumulation
Clean and protect the FQM1 if nec-
essary.
Check for water, oil, or chemi-
cal sprays hitting the FQM1.
No spray on the FQM1
Clean and protect the FQM1 if nec-
essary.
Check for corrosive or flam-
mable gases in the area of the 
FQM1.
No corrosive or flammable 
gases
Check by smell or use a sensor.
Check the level of vibration or 
shock.
Vibration and shock must 
be within specifications.
Install cushioning or shock absorb-
ing equipment if necessary.
Check for noise sources near 
the FQM1
No significant noise 
sources
Either separate the FQM1 and 
noise source or protect the FQM1.