Omron FQM1-CM001 ユーザーズマニュアル

ページ / 414
32
List of Models
Section 2-1
2-1
List of Models
Note
If CX-Programmer Ver. 5.0 is used with the FQM1, the FQM1 Patch Software
must be installed.
2-2
General Specifications
General Specifications
Name
Type
Model
Specifications
Coordinator Mod-
ule
Standard 
(with built-in I/O)
FQM1-CM001
Program capacity: 5 Ksteps
16 general-purpose inputs, 8 general-purpose outputs
Peripheral port, RS-232C port, RS-422A port
Motion Control 
Modules
Pulse I/O
FQM1-MMP21
Program capacity: 5 Ksteps
2 pulse inputs, 2 pulse outputs, 12 general-purpose 
inputs, 8 general-purpose outputs
Analog I/O
FQM1-MMA21
Program capacity: 5 Ksteps
2 pulse inputs, 1 analog input, 2 analog outputs, 
12 general-purpose inputs, 8 general-purpose outputs
End Module
Standard
FQM1-TER01
Connects to the right end of the FQM1.
Servo Relay Units
---
XW2B-80J7-1A
Simplifies wiring from the Motion Control Module to two 
Servo Drivers, wiring for all switches, sensors, and other 
general-purpose I/O, and wiring the RS-422A line.
FQM1 Flexible 
Motion Controller 
Set
Set for pulse I/O
FQM1S-MC231
A set including the CJ1W-PA202, FQM1-CM001, FQM1-
MMP21, and FQM1-TER01
Set for analog I/O FQM1S-MC222
A set including the CJ1W-PA205R, FQM1-CM001, 
FQM1-MMA21, and FQM1-TER01
Programming 
Device
CX-Programmer 
Ver. 5.0 or later
WS02-CXPC1-E-V5
(See note.)
Used for System Setup setting, programming, and moni-
toring for Coordinator Modules and Motion Control Mod-
ules. The FQM1 patch file is used with CX-Programmer 
Ver. 5.0.
Item
Specifications
Insulation resistance
20 M
Ω min. (at 500 VDC) between AC external and GR terminals (See note 1.)
Dielectric strength
2,300 V AC 50/60 Hz for 1 min between AC external and GR terminals (See notes 1 and 2.)
Leakage current: 10 mA max.
720 V AC 50/60 Hz for 1 min between DC external and GR terminals (See note 1.)
Leakage current: 10 mA max.
Noise immunity
2 kV on power supply line (conforming to IEC61000-4-4)
Vibration resistance
10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s
2
 in X, Y, and Z direc-
tions for 80 minutes total (Time coefficient: 8 minutes 
× coefficient factor 10 = total time 80 
min.) (conforming to JIS C0040)
Shock resistance
147 m/s
2
 3 times each in X, Y, and Z directions (conforming to JIS C0041)
Ambient operating tem-
perature
0 to 55
°C
Ambient operating 
humidity
10% to 90% (with no condensation)
Atmosphere
Must be free from corrosive gases
Ambient storage temper-
ature
−20 to 75°C
Grounding
Less than 100 
Ω
Enclosure
Mounted in a panel.
Dimensions
49 
× 90 × 80 mm (W × H × D) (not including cables)
Weight
All models are each 5 kg max.
Safety measures
Conforms to EC directives, C-Tick, and cULus.