Module Current Consumption
Section 2-6
XW2B-80J7-1A Servo Relay Unit
2-6
Module Current Consumption
The amount of current/power that can be supplied to the Modules mounted in
the FQM1 is limited. Refer to the following tables when designing your system
so that the total current consumption of the mounted Modules does not
exceed the maximum current for each voltage system and the total power
consumption does not exceed the maximum for the Power Supply Unit.
Maximum Current and 
Maximum Total Power 
Consumption
The following table shows the maximum currents and power that can be sup-
plied by Power Supply Units to the Controller.
Current Consumption for Each Module
Current Consumption for 5-V System
Note
The current consumption increases by 0.15 A/Module if NT-AL001 Link Adapt-
ers are used.
160
4.5 dia.
Phase B switches
Signal switches
Terminating resistance switch
100 90
41.7
15.9
30.7
Power Supply 
Unit
Max. current consumption
Max. total 
power con-
sumption
5-V system 
(internal logic)
24-V system 
(analog)
24-V system 
(service)
CJ1W-PA202
2.8 A
0.4 A
None
14 W
CJ1W-PA205R
5.0 A
0.8 A
None
25 W
Name
Model
5-V system current 
consumption (A)
Coordinator Module
Note The listed value includes the 
current consumption for the 
CX-Programmer.
FQM1-CM001
0.47 (See note.)
End Module
FQM1-TER01
Included in Coordinator 
Module current consumption