13 High Speed Processing – FNC 50 to FNC 59
13.6 FNC 55 – HSZ / High Speed Counter Zone Compare
11
FN
C
30
-FN
C
39
R
otati
on and 
Shi
ft
12
FNC4
0-F
NC4
9
D
ata O
per
ati
on
13
FN
C
50-FN
C
59
H
igh S
pe
ed 
P
rocessing
14
FM
C
60-FN
C
69
H
andy 
In
st
ru
ct
ion
15
FNC7
0-F
NC7
9
Ex
ter
nal FX
 I/O
 
D
evice
16
FN
C
80-FN
C
89
Ext
ernal
 FX 
De
vic
e
17
FN
C
100-
FN
C
10
9
Da
ta
 
Transf
er 2
18
FN
C
110-
FN
C
139
Floati
ng Poi
nt
19
FN
C
14
0-F
N
C
149
Da
ta
 
O
per
at
ion 2
20
FN
C
150-
FN
C
159
Posit
ioning 
C
ont
ro
l
2. Device specification range
Only high speed counters (C235 to C255) can be specified as 
.
3. Only 32-bit operation instructions are available.
Because instructions for high speed counters are dedicated to 32 bits, make sure to input "DHSZ (FNC 55)".
4. Caution on values set in the comparison value 1 
 and comparison value 2 
Make sure that 
 is smaller than or equivalent to 
.
5. Relationship between the comparison timing and the result output
1) DHSZ instruction executes comparison and outputs the result only when a counting pulse is input to a high speed
counter.
(When 
 is "1000" and 
 is "1999", the output 
 is set to ON as soon as the current value of C235
changes from "999" to "1000" or from "1999" to "2000".)
2) Because the comparison result cannot be obtained when restoring the power or when the PLC mode switches
from STOP to RUN, the result is not output even if the comparison condition is provided.
→ For details, refer to "13.6.1 Program in which comparison result is set to ON when power is turned ON [ZCP
(FNC 11) instruction]".
6. Priority order in operation among HSCS (FNC 53), HSCR (FNC 54), and HSZ (FNC 55) 
instructions for a same high speed counter
→ For details, refer to "6. Priority order in operation among HSCS (FNC 53), HSCR (FNC 54), and HSZ (FNC 55)
instructions for a same high speed counter" in Subsection 13.4.1.
7. Reset operation by an external terminal
→ For details, refer to "5. Reset operation by an external terminal [M8025*1: HSC (external reset) mode]" in
Subsection 13.4.1.
8. Number of occupied devices
1) The comparison value occupies two devices from 
 or 
 respectively.
2) The output occupies three devices from 
.
   
S
  
S
1
  
S
2
  
S
1
  
S
2
  
S
1
  
S
2
   
D
  
S
1
  
S
2
   
D