Lochinvar SMART TOUCH 1.3 ユーザーズマニュアル

ページ / 20
6
Parameters
Parameter information screens
By accessing the Parameter Information Screens on the
SMART TOUCH program, the installer can view all of the
SMART TOUCH parameters. The installer can also change
certain specific parameters to fine tune the operation of the
boiler to the installation. 
NOTE The PC cable must be connected to either the PC1 or
PC2 connection. When connected, the status screen on the
SYNC will show a communication error. This will clear
automatically when the cable is removed.
To access the parameter list, click on the Parameters button
along the top of the Main Screen window (FIG. 6-1). Next
click on Retrieve Parameters from Controller in the pull
down menu (see FIG. 6-1). This will upload the current
parameters in the SMART TOUCH to the PC. 
Figure 6-1 Parameters Pull-Down Menu Screen
Adjustable parameters are located in:
Set 1:
System Setup
Set 2:
Functional Data
Set 4:
Menu Values
While many parameters are viewable in each set, only select
parameters are adjustable. To make an adjustment to a
parameter, select the parameter to be changed from the
appropriate set. Click on the box next to the parameter and
type in the value for the parameter. 
Once an adjustment has been made to a parameter, it must be
programmed into the SMART TOUCH. On the Parameter
pull down menu, click on the Program Parameters into
Control 
button.  This will bring up another pull down menu.
If a parameter was changed in just one set, select the set from
the menu and click on it. If changes were made in multiple
sets, select the Store Parameter Set 0-4 from the menu and
click on it.  This will program the new parameters into the
SMART TOUCH.  If the parameters are based on a parameter
set from a different model, they may not be compatible with
this model.  In that case, the program will display a message to
let you know.  You may compare parameter 1AR in the
SMART TOUCH control, and in the new parameter file, to
determine if they are compatible.
While the programming is taking place, the SMART TOUCH
will go into a lockout mode. It will require that the Reset
button on the display be pressed after the programming has
been completed before the unit will be allowed to operate.
10
PC Program Instructions