Environmental control system  48 
The Basic System Configuration screen displays the basic alarm parameters, humidifier control, and fan 
controls. The configured parameters are only used to trigger an ECS alarm. The parameters listed on this 
screen do not configure the cooling system. 
 
You can select and configure the following parameters: 
 
Cold aisle temperature alarm 
 
Hot aisle temperature alarm 
 
Humidity alarm 
 
Differential pressure alarm 
 
Differential pressure filter alarm 
 
Chilled water supply pressure 
 
Chilled water supply temperature 
 
Chilled water return temperature 
 
Chilled water return pressure 
You must select Save to store the parameter changes in the system configuration file. If you do not save your 
changes, the old parameters stored in the configuration file reload when the system starts. 
 
Configuring the chilled water supply temperature alarm parameters 
The current temperature parameters appear on the related buttons.