Configuration, Startup, and Operation 
 
 
of Recorder with Display 
12/03 
DR4300 Circular Chart Recorder Product Manual 
103 
Lower Display 
Prompt 
Upper Display  
Range of Setting  
or Selection 
Parameter  
Definition 
PB2 
or 
GAIN 2 
 
0.1 % to 999.9 % 
or 
0.1 to 999.9 
[factory setting = 1.0]
 
RATE2T 
0.08 to 10.00 minutes 
0.08 or less = OFF 
 
[factory setting = 0.0]
 
I2 MIN  
or 
I2 RPM  
0.02 to 50.00 
 
 [factory setting = 0.02] 
PB2 
or GAIN 2, RATE2T, and I2 MIN or I2 RPM
These parallel their counterparts already described.  
ATTENTION
 If control group parameter “OUTALG” 
is “RLYD” (relay duplex), “Tcur” (time/current duplex), or 
“CurT” (current/time duplex), and you are using the 
recorder in a heat/cool application, these parameters are 
used for cooling control. 
The following parameters are used for time proportional control, and are available only if: 
•  the control type specified in the control set up group using the “CTRALG” (control algorithm) 
parameter is “PIDA” or “PDMR” 
 
and 
•  the output algorithm specified in the control set up group using the “OUTALG” parameter is  
“RLY” , “RLYD”, “CurT”, or “Tcur”.  In the case of “CurT” and “Tcur”, the cycle parameters apply only to 
the time-proportioned output. 
CYC TI 
0 seconds to 120 seconds 
[factory setting = 4]
 
 
CYCLE TIMER FOR RELAY 1
—Use this to specify 
length of total cycle time for time proportional control 
(proportional control using relay action rather than current 
output). In time proportional control the output (0 % to 100 
%) signifies the portion of the cycle for which the relay is 
on (“duty cycle”) to achieve the desired setpoint. For 
example, with a 10-second cycle time and an output value 
of 10 %, the relay would be on for 1 second and off for 9 
seconds. 
ATTENTION
 If control group parameter “OUTALG” is 
“RLYD” (relay duplex), and you are using the recorder in 
a heat/cool application, CYC TI is used for heat control. 
Cooling control would use CYC2TI. 
CYC2TI  
0 seconds to 120 seconds 
[factory setting = 4]
 
 
CYCLE TIMER FOR RELAY 2
—This prompt will be 
displayed only if the control group parameter “OUTALG” 
is set to RLYD (relay duplex). 
ATTENTION
 If you are using the recorder in a 
heat/cool application, CYC2TI is used for control of 
cooling.