Configuration, Startup, and Operation 
 
 
of Recorder with Display 
12/03 
DR4300 Circular Chart Recorder Product Manual 
107 
Lower Display 
Prompt 
Upper Display  
Range of Setting  
or Selection 
Parameter  
Definition 
A1S1HL 
 
 
 
 
HI 
 
LO      [factory setting] 
ALARM 1 SETPOINT 1 STATE
—Select whether you 
want the alarm type chosen in prompt "A1S1TY" to alarm 
high or low.  
HI ALARM
—Relay coil is de-energized when the PV is 
above
 the setpoint.  
LO ALARM—Relay coil is de-energized when the PV is 
below
 the setpoint. 
A1S2HL 
 
 
 
 
HI      [factory setting] 
 
LO 
ALARM 1 SETPOINT 2 STATE
—Select whether you 
want the alarm type chosen in prompt "A1S2TY" to alarm 
high or low. 
HI ALARM
—Relay coil is de-energized when the PV is 
above
 the setpoint. 
LO ALARM—Relay coil is de-energized when the PV is 
below
 the setpoint. 
A1 HYS 
0.0 % to 100.0 % of input 
span 
 
[factory setting = 0]
 
ALARM 1 HYSTERESIS
—This is an adjustable 
hysteresis provided on alarm 1 that activates at exactly 
the alarm setpoint when the alarm is OFF. When the 
alarm is ON, it will not deactivate until the variable is away 
from the alarm setpoint by a value equal to A1 HYS. 
Configure the hysteresis as a percent of input range 
span.  
A2S1TY 
Same as A1S1TY 
ALARM 2 SETPOINT 1 TYPE
—Select what you want 
Setpoint 1 of Alarm 2 to represent. The selections are the 
same as “A1S1TY”. 
A2S2TY 
Same as A1S1TY 
ALARM 2 SETPOINT 2 TYPE
—Select what you want 
Setpoint 2 of Alarm 2 to represent. The selections are the 
same as “A1S1TY”. 
A2S1VA 
–999 to 9999 
 
[factory setting = 100]
 
ALARM 2 SETPOINT 1 VALUE
—This is the value at 
which you want the alarm type chosen in prompt 
"A2S1TY" to actuate. The appropriate value depends on 
what the setpoint has been configured to represent. 
A2S2VA 
–999 to 9999 
 
[factory setting = 100]
 
ALARM 2 SETPOINT 2 VALUE
—This is the value at 
which you want the alarm type chosen in prompt 
"A2S2TY" to actuate. The appropriate value depends on 
what the setpoint has been configured to represent. 
A2S1HL 
 
 
 
 
HI 
 
LO    [factory setting] 
ALARM 2 SETPOINT 1 STATE
—Select whether you 
want the alarm type chosen in prompt "A2S1TY" to alarm 
high or low.  
HI ALARM
—Relay coil is de-energized when the PV is 
above
 the setpoint. 
LO ALARM—Relay coil is de-energized when the PV is 
below
 the setpoint. 
A2S2HL 
 
 
 
 
HI    [factory setting] 
 
LO 
ALARM 2 SET POINT 2 STATE
—Select whether you 
want the alarm type chosen in prompt "A2S2TY" to alarm 
high or low. 
HI ALARM
—Relay coil is de-energized when the PV is 
above
 the setpoint. 
LO ALARM—Relay coil is de-energized when the PV is 
below
 the setpoint.