Honeywell VCR DCP200 ユーザーズマニュアル

ページ / 184
DCP200 Profile Controller & Recorder - Product Manual
51-52-25-150, Issue 1 – April 2009
Modbus Parameters
Page 109
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Real Time Clock 
Fitted
7871
0x1EBF
RO
Value
Real Time Clock Fitted
0
Not Fitted
1
Fitted
Day Of The Week
7872
0x1EC0
R/W
Value
Day Of Week
1
Monday
2
Tuesday
3
Wednesday
4
Thursday
5
Friday
6
Saturday
7
Sunday
Display Parameters
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
LED 1 Label
7660
0x1DEC
R/W
5 ASCII characters, which can re read or written using 
Modbus functions 16 or 23. Valid characters are 0 to 
9, a to z, A to Z, plus ( )  - and _.
Defaults: 1 = PRI (Primary); 2 = SEC (Secondary);
3 = TUNE (Tuning); 4 = ALARM (Alarm)
LED 2 Label
7661
0x1DED
R/W
LED 3 Label
7662
0x1DEE
R/W
LED 4 Label
7663
0x1DEF
R/W
LED 1 Usage
7664
0x1DF0
R/W
Value
LED 1 Usage
0
Primary Control
1
Secondary Control
2
Tuning
3
Any Alarm
4
Alarm 1
5
Alarm 2
6
Alarm 3
7
Alarm 4
8
Alarm 5
9
Event 1
10
Event 2
11
Event 3
12
Event 4
13
Event 5
14
Any Event
15
Manual Control
16
Profile Running
17
Profile Ended
LED 2 Usage
7665
0x1DF1
R/W
Value
LED 2 Usage
0
Primary Control
1
Secondary Control
2
Tuning
3
Any Alarm
4
Alarm 1