Honeywell VCR DCP200 ユーザーズマニュアル

ページ / 184
DCP200 Profile Controller & Recorder - Product Manual
51-52-25-150, Issue 1 – April 2009
Calibration
Page 131
Recalibration Procedure
Recalibration is carried out in five phases as shown in the table below; each phase 
corresponds to a basic input type.
CAUTION:
The 50mV phase MUST be calibrated before the thermocouple range.
Table 27. Input Calibration phases
DC milli-volt Calibration
50 mV
DC voltage Calibration
10 V
DC milliamps Calibration
20 mA
RTD Calibration
200 ohm
Thermocouple Calibration
K type source at 0ºC
1. For optimum accuracy, power-up the instrument for 30 minutes, then toggle the power 
off/on to restart the instrument.
2. During the power-up “splash screen”, press 
and 
together until the Calibration 
Status screen is displayed.
3. Press 
to select the first calibration phase (50mV Calibration)
4. Ensure that an accurate 50mV signal has been applied to terminals 2 (+ve) and 3 (-ve), 
then press 
to initiate the calibration.
5. During calibration the message “50mV DC Input Calibrating” will display for a few 
seconds. This should be followed by the “Calibration Successful” confirmation.
6. If the input is misconnected or an incorrect signal is applied, the calibration will be aborted 
and the display will show “Failed: Signal Too Small!” or “Failed: Signal Too Large!”.
The previous calibration value will be retained.
7. Press 
to select the next calibration phase.
8. Repeat this process for each input type until all the phases are calibrated. For each phase, 
ensure that the correct input is applied, using the correct connections.
9. Once all calibration phases are completed, recorder versions will display the Calibration 
Reminder Date. If required, this can be changed to the date of your next calibration check. 
Ensure that Calibration Reminders are enabled in Input Configuration to receive a 
reminder.
10.Press 
to exit to the main menu.
Note:
Calibration Mode automatically exits if there is no button activity for two minutes.