DCP200 Profile Controller & Recorder - Product Manual
Page 26
Electrical Installation
51-52-25-150, Issue 1 – April 2009
13
14
L
N

The wiring diagram below shows the additional connections (numbered 25 to 42) at the 
sides of the case rear. These are required for Options Slots 4 and C if fitted.
Figure 8. Additional Option terminals
Note:
Use single strand (1.2mm / AWG18 max size) copper wire throughout, except for the 
thermocouple input, where the correct thermocouple or compensating cable and 
connectors must be used.
Power Connections
Power Connections - Mains Powered Instruments
Mains powered instruments operate from a 100 to 240V (±10%) 50/60Hz supply.  Power 
consumption is 24VA. Connect the line voltage (live and neutral) as illustrated via a two-pole 
IEC60947-1 & IEC60947-3 compliant isolation switch / circuit breaker and a UL listed fuse 
type: 250V AC 1Amp anti-surge. If the instrument has relay outputs with contacts carrying 
mains voltage, it is recommended that the relay contacts supply should be switched and 
fused in a similar manner, but should be separate from the instruments mains supply. 
Figure 9. Mains Power Connections
WARNING:
CHECK THE INFORMATION LABEL ON THE CASE TO DETERMINE THE CORRECT 
VOLTAGE BEFORE CONNECTING TO A LIVE SUPPLY.
CAUTION:
This equipment is designed for installation in an enclosure that provides adequate 
protection against electric shock. The isolation switch should be located in close 
proximity to the unit, in easy reach of the operator and appropriately marked.