Honeywell VCR DCP200 ユーザーズマニュアル

ページ / 184
DCP200 Profile Controller & Recorder - Product Manual
51-52-25-150, Issue 1 – April 2009
Profiler Option
Page 71
Profile Cycles & Repeat Sequences
A profile can be configured to run itself 1 to 9999 times or continuously using the Profile 
Cycles setting. A profile ending with Repeat Then End will run the entire sequence of 
profiles again from 1 to 9999 times before ending.
PROFILE 4
PROFILE 31
PROFILE 7
Join (Profile 4 to Profile 31)  
Join (Profile 31 to Profile 7)
Figure 43.
Profile Cycles & Repeats
Power/Signal Lost Recovery Actions
If there is a power cut while a profile is running, the instrument will use the defined Profile 
Recovery Method 
once the power has been restored.
If there is a break in the input while a program is running, the unit will go to the Pre-Set 
Power Value during the break condition. Once the condition has ended it carries out the 
same recovery action as specified for power failure.
Note:
Recorder versions always use option E (Continue profile from the point it had reached 
when the power failed) if the Power Off Time is less than the Profile Recovery Time 
setting. If the power is off for more than this time, the defined Profile Recovery Method is 
used.
Example:
Runs profile 4 once, 
profile 31 three times 
& profile 7 once.
This sequence is 
repeated ten times.
Profile 31 
Cycles = 3
Repeat Sequence = 10
Repeat Then End
(times to repeat = 10)
Profile 4 
Cycles = 1
Profile 7 
Cycles = 1