DCP200 Profile Controller & Recorder - Product Manual
51-52-25-150, Issue 1 – April 2009
Serial Communications
Page 81
Function 06 - Write Single Register
Writes two bytes to a specified word address. 
QUERY
Function
Address of Word
Value to write
06
HI
LO
HI
LO
RESPONSE
Function
Address of Word
Value written
06
HI
LO
HI
LO
Note:
The Response normally returns the same data as the Query.
Function 08 - Loopback Diagnostic Test
QUERY
Function
Diagnostic Code
Value
08
HI =00
LO=00
HI
LO
RESPONSE
Function
Sub-function
Value
08
HI=00
LO=00
HI
LO 
Note:
The Response normally returns the same data as the loopback Query. Other Diagnostic 
Codes are not supported.
Function 16 - Write Multiple Registers (0x10 Hex)
Writes consecutive word (two-byte) values starting at the specified address.
QUERY
Function
1
st
Write 
Address
Number of 
Words to Write
Number of 
Query Bytes
1
st
Query 
Byte
2
nd
Query 
Byte
etc
Last Query 
Byte
10
HI
LO
HI
LO
RESPONSE
Function
1
st
Word Address
Number of Words
10
HI
LO
HI
LO
Note:
The number of data bytes that can be written in one message is 253 bytes.