Honeywell VCR DCP200 ユーザーズマニュアル

ページ / 184
DCP200 Profile Controller & Recorder - Product Manual
Page 90
Modbus Parameters
51-52-25-150, Issue 1 – April 2009
Option Slot 2 Parameters
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Option Slot 2 
Module Type
2160
0x0870
RO
Value
Module Fitted In Slot 2
0
None Fitted
1
Single Relay
2
Single SSR Driver
3
Linear mA/V DC
8
Triac
9
Dual Relay
10
Dual SSR Driver
11
24VDC Transmitter PSU
255
Error (unrecognised module)
Linear mA/V DC 
Output 2 Type
2161
0x0871
R/W
Value
Linear Output 2 Type
0
0 to 5V DC
1
0 to 10V DC
2
2 to 10V DC
3
0 to 20mA DC
4
4 to 20mA DC
5
Variable 0 to 10VDC Transmitter PSU
Digital Output 2 or 
2A Status
2162
0x0872
RO
Value
Digital Output 2 or 2A Status
0
Inactive
1
Active
Digital Output 2B 
Status
2163
0x0873
RO
Value
Digital Output 2B Status
0
Inactive
1
Active
Linear Output 2 
Level Status
2164
0x0874
RO
-2.0% to 102.0% of nominal range
(control output will over/under drive by 2%).
Linear Output 2 or 
2A Function
2174
0x087E
R/W
Value
Linear Output 2 or 2A Function
0
Disabled
1
Primary Output Power
2
Secondary Output Power
3
Retransmit Actual Setpoint Value
4
Retransmit Process Variable Value
Digital Output 2 or 
2A Function
2176
0x0880
R/W
Value
Digital Output 2 or 2A Function
0
Disabled
1
Primary Output Power
2
Secondary Output Power
3
Alarm
4
Alarm and Event