Honeywell VCR DCP200 ユーザーズマニュアル

ページ / 184
DCP200 Profile Controller & Recorder - Product Manual
51-52-25-150, Issue 1 – April 2009
Modbus Parameters
Page 93
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
20
Event 4 AND Alarm 4. Direct Acting
21
Event 4 AND Alarm 4. Reverse Acting
22
Event 5 AND Alarm 5. Direct Acting
23
Event 5 AND Alarm 5. Reverse Acting
Output 2 Retransmit 
Minimum
2182
0x0886
R/W
Limited by input range maximum/minimum
Output 2 Retransmit 
Maximum
2183
0x0887
R/W
Limited by input range maximum/minimum
Option Slot 3 Parameters
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Option Slot 3 
Module Type
2192
0x0890
RO
Value
Module Fitted In Slot 3
0
None Fitted
1
Single Relay
2
Single SSR Driver
3
Linear mA/V DC
8
Triac
9
Dual Relay
10
Dual SSR Driver
11
24VDC Transmitter PSU
255
Error (unrecognised module)
Linear mA/V DC 
Output 3 Type
2193
0x0891
R/W
Value
Linear Output 3 Type
0
0 to 5V DC
1
0 to 10V DC
2
2 to 10V DC
3
0 to 20mA DC
4
4 to 20mA DC
5
Variable 0 to 10VDC Transmitter PSU
Digital Output 3 or 
3A Status
2194
0x0892
RO
Value
Digital Output 3 or 3A Status
0
Inactive
1
Active
Digital Output 3B 
Status
2195
0x0893
RO
Value
Digital Output 3B Status
0
Inactive
1
Active
Linear Output 3 
Level Status
2196
0x0894
RO
-2.0% to 102.0% of nominal range
(control output will over/under drive by 2%).
Linear Output 3 or 
3A Function
2203
0x089B
R/W
Value
Linear Output 3 or 3A Function
0
Disabled
1
Primary Output Power
2
Secondary Output Power
3
Retransmit Actual Setpoint Value
4
Retransmit Process Variable Value