Enviro EA800 ユーザーズマニュアル

ページ / 98
14
D-011-0152
Sensors
Sensor Parameter Descriptions
This section provides a description of each sensor parameter.
Table 11
Sensor Parameter Descriptions
Parameter
Applicable to Sensors
Description
Sensor Name All
A name used to identify the sensor in the alarm system. Select a name 
readily identified by the viewer. The sensor name is displayed on the 
Main screen during a no-alarm condition and on the Alarm screen during 
an alarm condition. Two name choice types are available:
• Common Name: These are preprogrammed names.
• Custom Name: This selection allows you to enter any name if the 
preprogrammed common names do not adequately identify the sensor 
in the system (limited to 16 characters).
Note: Duplicate sensor names are not permitted.
Unit of 
Measure
• Blue, Red and White 
temperature sensors
• 4-20mA sensor
• Wireless 
temperature sensors
This parameter allows you to choose the unit of measure used for sen-
sor reading and display.
• Blue, Red and White temperature sensors: °C or °F
• 4-20mA sensors: the following Common Units of measure are 
available: F (Fahrenheit), C (Centigrade), K (Kelvin), % rh (percent 
relative humidity), psi (pounds per square inch), Pa (Pascals), kPa 
(kiloPascals), lb (pound), kg (kilogram)
• 4-20mA sensors can also use custom units. Enter the appropriate units 
for the connected 4-20mA sensor via the keypad.
Resolution
4-20mA sensor
This determines the range that may be used for the 4-20mA sensor. The 
full scale range is determined by the values entered in the Low Scaled 
Value and the High Scaled Value. You must select the correct resolution 
in order to set the true range limits for the 4-20mA sensor you are install-
ing. The available values are as follows:
Maximum Allowed 
Maximum  Allowed
Resolution
Low Scaled Value
High Scaled Value
1.
-9999.
+9999.
0.1
-999.9
+999.9
0.01
-99.99
+99.99
0.001
-9.999
+9.999
Low Scaled 
Value
4-20mA sensor
This parameter equals the environmental reading that results in a sensor 
output of 4mA or its minimum valid reading. This is dependent on the 
setting of the resolution as discussed above.
High Scaled 
Value
4-20mA sensor
This parameter equals the environmental reading that results in a sensor 
output of 20mA or its maximum valid reading. This is dependent on the 
setting of the resolution as discussed above.
Hysteresis
• Blue, Red and White 
temperature sensors
• HA-III+
• 4-20mA sensor
The Hysteresis setting helps prevent alarms from being set and reset 
continually if the environment is at or near the alarm set point by provid-
ing an acceptable variance. For example, if Hysteresis is set at 2 and the 
sensor High limit is set at 50, the sensor reading must decrease to 48 
(50 minus 2) in order for the alarm condition to reset to a no-alarm condi-
tion.
Low Alarm 
Limit
• Blue, Red and White 
temperature sensors
• HA-III+
• 4-20mA sensor
• Wireless humidity 
sensor
• Wireless 
temperature sensor
The Low Alarm Limit sets the value that trips the low alarm when 
exceeded.