Enviro EA800 ユーザーズマニュアル

ページ / 98
68
D-011-0152
Exporting the Stored Logs
Exporting the Stored Logs
You can export the logs stored in the EA800 for archiving or later review. The export procedure exports the alarm 
log, data log, and event log files. To export the logfiles perform the following procedure:
The EA800 stores the log files on the USB drive in comma separated value (CSV) format. The files are named in 
the format XYYMMDD-HHMMSS.txt where:
X = A, E, or D:
A = Alarm log file
E = Event log file
D = Sensor data log file
YYMMDD is the current date.
HHMMSS is the current time in 24 hour format.
You can rename the files to more easily identify the EA800 system they came from, however, the first character 
designating the log type (A, E, or D) must be retained if using the template available at www.winland.com. Because 
the files are in CSV format they can be converted to tables in a word processing program or imported into a 
spreadsheet program.
Exported Alarm Data
The following is an example of exported alarm data:
12/27/2007 01:28:39 ,3,Laundry Room,Wet,Dry,Dry,,Wired,WaterBug,1
12/27/2007 01:29:10 ,3,Laundry Room,Dry,Dry,Dry,,Wired,WaterBug,0
12/27/2007 02:38:45 ,4,Cooler #3,67,-58,158,F,RF Contact,Blue,4
12/27/2007 02:39:48 ,4,Cooler #3,67,-58,158,F,RF Contact,Blue,0
12/27/2007 07:10:45 ,3,Laundry Room,Wet,Dry,Dry,,Wired,WaterBug,1
12/27/2007 07:10:50 ,3,Laundry Room,Dry,Dry,Dry,,Wired,WaterBug,0
The data presented provides the following alarm information:
Date and time 
of reading
Sensor 
Number
Sensor 
Name
Sensor 
Reading
(at time of 
alarm)
Low 
Limit 
Value
High 
Limit 
Value
Unit of 
Measure
Sensor 
Connection
Sensor 
Type
Code
12/27/2007 
01:28:39
3
Laundry 
Room
Wet
Dry
Dry
N/A
Wired
WaterBug 1
F3
To return to 
SELECT SENSOR
 screen
To return to home screen.
OR
Appears only if a USB 
drive is not installed
The screen displays 
the progress of the 
data export. Remove 
USB drive when 
export is complete.