    1.  Product Information
  1.1  Function
Use 
 
The EXHAUSTO RSIB Power Venter is intended for use as an in-line draft inducer/power venter.  
 
 
 
It can be installed in-line with the chimney or stack, and can be used in sidewall and vertical venting  
 
 
 
arrangements. It is specifically designed for applications requirinng efficient operation, low noise level, low  
 
 
energy consumption, variable speed and compact design. The RSIB is for use with non-condensing  
 
 
 
and condensing appliances (Category I, II, III, IV) operating at flue gas temperatures at or below 575°F    
 
 
(300° C). Typical uses include, but are not limited to, mechanical venting of gas and oil fired boilers and    
 
 
water heaters and other appliances operating with discharge temperatures at or below 575°F (300° C).     
 
 
The RSIB is for indoor and outdoor installations.
Construction  
The EXHAUSTO RSIB Power Venter is an efficient high temperature ventilator with a backward-inclined,
 
 
cast aluminum impeller. The ventilator housing is made of corrosion resistant 316L stainless steel.  It  
 
is equipped with an energy-efficient, totally enclosed, variable speed motor, which is mounted outside  
 
 
the air stream.  A motor mounting plate on the front of the ventilator provides easy access to the inside    
 
 
of the fan and the duct connections.  The motor and impeller are mounted on the motor mounting  
 
 
 
plate which is secured to the fan housing with six bolts. The stack connections are of the slip connection   
 
 
type.  The ventilator can be mounted on vibration insulated support legs or from ceiling mounting brackets.
Listings    
The RSIB model is tested and listed to UL378, Standard for Draft Equipment, UL705, Standard for Power  
 
 
Venters, and CSA-CAN3-B255-M81, Mechanical Flue Gas Exhausters.  The Canadian listing does not    
 
 
cover use with condensing appliances.  This installation manual does not contain any system design  
 
 
 
documentation.  Please refer to the system design manuals or instructions by EXHAUSTO.  The RSIB is a  
 
 
component in the CASI, Chimney Automation System.
Restrictions  
The RSIB Power Venter should only be used with appliances operating on Natural Gas, LP-Gas/Butane    
 
 
or fuel oil (#2 through #6).  It should never be used with incinerators, incinerating toilets or solid-  
 
 
 
fuel burning equipment.  When used with multiple appliances and utilizing a Fan Speed Control or  
 
 
 
a Variable Frequency Drive to control the fan speed, a barometric damper should be installed to prevent   
 
 
overdraft conditions, unless the appliance(s) has a draft hood or a draft diverter.  This limitation does  
 
not apply when used with an EBC 12 or EBC 30, Pressure Control. The temperature of the flue gases  
 
 
going through the Power Venter should never exceed 575°F (300°C).
  1.2  Components
Mounting eyes 
and holes
Outlet
Mounting 
legs
Motor
Motor Mounting 
Plate
Fig. 1