EMC 4K VA 20K VA UPS ユーザーズマニュアル

ページ / 23
 
30 
Net Weight kg (lb) 
W/O ISOTR   
                          50 (110) 
86.0 (189.2)   
80(176)  
Shipping Weight kg 
(lb) W/O ISOTR   
                          53 (116.7) 
106.0 (233.2)   
101.5(223.3)  
Dimensions W x D 
x H mm (inch) W/ 
ISOTR  
257 x 590 x 700 
(10.1"x23.2"x27.6") 
342 x 690 x 715 
(13.4" x 27.2" x 
28.1")  
Net Weight kg (lb) 
W/ ISOTR   
123.0 (270.6)   
130 (286.0)   
Shipping Weight kg 
(lb) W/ ISOTR   
 
145.0 (319.0)   
151.5 (333.3)   
Operating 
Temperature  
0~40°C / 32~104°F  
Storage 
Temperature  
-20~50°C / -4~122°F  
Altitude  
3,500 meters max   
Audible Noise (1 
meter from surface) 
50 dBA 
< 55 dBA   
Environment 
Relative Humidity   
0 ~ 95% humidity, non-condensing   
Safety  
UL 1778, CE   
EMC (EMS / EMI)   
IEC 61000-4, FCC Part 15, CISPR 22   
Conformance 
Equipment 
Protection Policy   
Warranty policy may vary depends on region   
 
 
Tower model (with LCD display)   
VGD-10000  
VGD-12000  
VGD-15000  
VGD-20000  
Capacity (VA)   
10000VA  
12000VA  
15000VA  
20000VA  
Capacity 
Capacity (W)   
7000W  
8400W  
10500W  
14000W  
Voltage (on battery) 
100V, 110V, 115V, 120V / 208V, 220V, 230V, 240V +/-2% (Selectable Output Voltage) 
Frequency (on 
battery)  
50 / 60 Hz +/-0.5%   
Transfer Time   
0 ms   
Overload Recovery 
Auto transfer to UPS   
High Efficiency 
mode (AC to AC)   
> 97 %   
UPS Design 
Technology  
On-Line / Fully digitized microprocessor controlled   
Output Wave Form 
Sine wave   
Harmonic distortion 
< 3% of T.H.D. at linear load   
Output  
Crest Factor   
3 : 1   
Surge Protection 
IEC61000-4-5 level 3   
Overload Protection 
125% for 1 minutes and 150% for 10 seconds (On-line) 130% for 10 seconds and 150% 
for 1.5 seconds (On-battery)   
Protection and 
Filtering 
Short Circuit 
Protection  
UPS output cut off immediately or input fuse / circuit breaker protection   
Visual Display (LED 
model)  
UPS on(green), line-mode(green), battery mode(yellow), bypass(yellow), fault(red)   
Visual Display 
(LCD model)   
Input / output voltage, input / output frequency, on-line mode, back up mode, battery 
capacity, load level   
Audible Alarm 
(Battery back-up)   
Beep every 5 sec   
UPS Fault   
Continuous beeping sound and LCD display   
System/Display
/Warning  
Communication  
RS-232 Serial Port and USB   
Type  
Sealed, maintenance-free lead acid batteries   
DC Voltage (V) 
Battery (Tower )   
240V / 12V9AH 
 x 20  
240V / 12V7.2AH 
x 20 x 2SET   
240V / 12V7.2AH 
  x 20 x 2SET   
240V / 12V9AH   
x 20 x 2SET   
Typical Recharge 
Time to 90% Full   
4 hours   
Management  
Self-test, adjustable battery transfer points and alarm settings   
Battery 
Battery Protection   
Cut off without draining any current when battery is low   
 
31
Cold Start (DC 
start)  
YES  
Back Up Time 
(Tower model)   
About 4~6 min Full load / 10~15min Half load   
Input Inlet   
Hardwire  
Receptacles  
Hardwire  
Dimensions W x D 
x H mm (inch) W/O 
ISOTR  
257 x 690 x 715 
(10.1" x 27.2" x 
28.1")  
342 x 690 x 905 
(13.5"x27.2"x35.6") 
342 x 760 x 905 (13.5" x 29.9" x 35.6")   
Net Weight kg (lb) 
W/O ISOTR   
80 (176)   
130 (286)   
207 (455.4)   
Shipping Weight kg 
(lb) W/O ISOTR   
101.5 (223.3)   
151.5 (333.3)   
225 (495.0)   
Dimensions W x D 
x H mm (inch) W/ 
ISOTR  
342 x 690 x 715 
(13.4" x 27.2" x 
28.1")  
342 x 690 x 905 
(13.5"x27.2"x35.6") 
342 x 760 x 905 (13.5" x 29.9" x 35.6")   
Net Weight kg (lb) 
W/ ISOTR   
130 (286)   
180 (396)   
274 (602.8)   
Physical 
Shipping Weight kg 
(lb) W/ ISOTR   
151.5 (333.3)   
201.5 (443.3)   
292 (642.4)   
Operating 
Temperature  
0~40°C / 32~104°F  
Storage 
Temperature  
-20~50°C / -4~122°F  
Altitude  
3,500 meters max   
Audible Noise (1 
meter from surface) 
< 55 dB   
Environment 
Relative Humidity   
0 ~ 95% humidity, non-condensing   
Safety  
UL 1778, CE   
EMC (EMS / EMI)   
IEC 61000-4, FCC Part 15, CISPR 22   
Conformance
Equipment 
Protection Policy   
Warranty policy may vary depends on region   
 
For Rack mount model 
RM model (with LCD display)   
VGD-4000 
VGD5000 
VGD-6000  
VGD-10000  
Capacity (VA)   
4000VA 
5000VA 
6000VA  
10000VA  
Capacity 
Capacity (W)   
2800W 
3500W 
4200W  
7000W  
Voltage (on battery) 
208V, 220V, 230V, 240V +/-2% (Selectable Output Voltage)   
Frequency (on 
battery)  
50 / 60 Hz +/-0.5%   
Transfer Time   
0 ms   
Overload Recovery 
Auto transfer to UPS   
High Efficiency 
mode (AC to AC)   
> 95 % 
> 97 %   
UPS Design 
Technology  
On-Line / Fully digitized microprocessor controlled   
Output Wave Form 
Sine wave   
Harmonic distortion 
< 3% of T.H.D. at linear load   
Output  
Crest Factor   
3 : 1   
Surge Protection 
IEC61000-4-5 level 3   
Overload 
Protection  
125% for 1 minutes and 150% for 10 seconds (On-line) 130% for 10 seconds and 150% 
for 1.5 seconds (On-battery) 
Protection and 
Filtering 
Short Circuit 
Protection  
UPS output cut off immediately or input fuse / circuit breaker protection   
Visual Display 
(LED model)   
UPS on(green), line-mode(green), battery mode(yellow), bypass(yellow), fault(red)   
Visual Display 
(LCD model)   
Input / output voltage, input / output frequency, on-line mode, back up mode, battery 
capacity, load level   
Audible Alarm 
(Battery back-up)   
Beep every 5 sec   
System/Display
/Warning  
UPS Fault   
Continuous beeping sound and LCD display