3.1.3.2
Electrical Wiring Cont'd
( )
5.
Connect each lighting load to the respective LOOP terminals
in the high voltage section, using the #12 AWG ring
terminals provided.
in the high voltage section, using the #12 AWG ring
terminals provided.
NOTE: BEFORE CONNECTING LOAD TO LOOP
TERMINALS, REMOVE JUMPER FROM ONLY THOSE
TERMINALS THAT LOAD IS BEING CONNECTED TO.
TERMINALS, REMOVE JUMPER FROM ONLY THOSE
TERMINALS THAT LOAD IS BEING CONNECTED TO.
( )
6.
Make any option related connections.
( )
7.
Re-install the dead front cover and fasten securely.
3.1.4
Option -1, De-Energized Switching, Disabling
( )
1.
To disable de-energized switching feature, move E2 spring
shunt on 31955 circuit assembly from E2-2/E2-3 to E2-1/E2-
2, refer to Figure 3C.
shunt on 31955 circuit assembly from E2-2/E2-3 to E2-1/E2-
2, refer to Figure 3C.