4
 
Minor Error Codes
The meaning of each Minor Error Code depends upon the Major Error Code for which it is
defined.  Consult the appropriate Minor Error Code table for the indicated Major Error Code.
Minor Error Codes for Major Error Codes 90H (Client API Error)
Error Status
Service Request Error Description
(Hexadecimal)
8190H
COMMREQ data block too short for the command.
8390H
Invalid server memory type.
8690H
Zero server unit length is not allowed.
8790H
Device unit length is too large.
8890H
Invalid channel number.
8C90H
Invalid client memory type.
8D90H
Invalid server host address type. (Must be 1.)
8E90H
Invalid IP address integer type. (Must be 0-255)
8F90H
Invalid IP Address class. (Developer’s note: Something wrong with
individual addresses.)
9090H
Insufficient TCP connection resources to do request.
9190H
Zero local starting address is not allowed.
9290H
Address length value invalid. Must be 4 for IP address type.
9590H
Internal API Error. See PLC Fault Table or exception log for details.
This problem may occur due to the Ethernet Interface being asked to
perform beyond its capacity.
9690H
Underlying TCP connection aborted (reset) by server end point.
9790H
Underlying TCP connection aborted (reset) by client end point.
9D90H
Data response had unexpected size.
9E90H
Unrecognized COMMREQ command code.
A190H
Invalid CRS word memory type.
A290H
Failed an attempt to update the CRS word.
B490H
The channel the application is trying to open is already open by
Modbus/TCP.
B590H
The channel the application is trying to access is owned by a different
protocol.