Appendix D  Using the IC697CMM742 with PLC CPU Versions 4.12 - 5.50
D-5
D
 
10. 
Use the SOSW Station Manager command to verify that all configuration parameters have
been set to the proper values. A typical SOSW command is shown below:
* sosw
<<< Soft Switch Data >>>
IP Address   = 10.0.0.1        (TCP/IP values from
Soft Switches)
Subnet Mask  = 0.0.0.0
Gateway      = 0.0.0.0
Name Server  = 0.0.0.0
Port 1 (Station Manager):      Port 2 (S/W Loader):
Data Rate      = 9600          Data Rate     = 19200
Parity         = NONE          Parity        = ODD
Stop Bits      = 1             Stop Bits     = 1
Flow Control   = NONE          Flow Control  = NONE
TurnA Delay    = NONE          TurnA Delay   = NONE
Timeout        = LONG          Timeout       = LONG
Source of Soft Switches: Internal Backup
11. When all configuration parameters have been correctly entered, use the RESTART Station
Manager command to restart the Ethernet Interface into normal operation.
The RESTART command is shown below:
= restart
Restarting module
The Ethernet Interface is restarted into the Operational state. After approximately 20 seconds,
another NODE output is automatically generated when the restart is complete. The NODE
output should indicate the IP Address configured in Step 9, above. (The Subnet Mask,
Gateway IP Address and Name Server IP Address can be displayed by the SOSW command,
as described in Step 10, above.)  The Ethernet Interface is now properly configured and ready
for use.
Please proceed to the Installation chapter to verify proper operation of the Ethernet Interface
with the new configuration data.