FANUC Robotics America GFK-1541B ユーザーズマニュアル

ページ / 240
2-45
2
 
Installing the CMM742 in the PLC
For general information about module and system installation, refer to GFK-0262, Series 90-70
Programmable Controller Installation Manual
.
Equipment Required to Perform the Installation Procedures
Make sure you have the items listed below before you begin.
ƒ 
Series 90-70 PLC rack.
ƒ 
Series 90-70 power supply.
ƒ 
To use the AUI port, the power supply must be one of the following types, which
provide +12 Vdc for an external transceiver on the AUI port: IC697PWR711,
IC697PWR724,  or IC697PWR748.
ƒ 
If the AUI port will not be used, +5 Vdc is all that is required.  Under these conditions,
power supply IC697PWR710 is sufficient.
ƒ 
A Series 90-70 CPU.
ƒ 
PLC programming software:  Logicmaster 90-70 version 6.02 or higher or Control version
1.0 or higher (runs on a personal computer).
ƒ 
Ethernet cables and, if using the AUI port, an Ethernet-compatible AUI transceiver.  (See
Appendix B, “Communications Ports Characteristics”, for more information.)
ƒ 
A serial cable for the Station Manager port on the Ethernet Interface (see Appendix B).
Optional
ƒ 
A terminal or IBM-compatible personal computer equipped with terminal emulation
software.  Optional
ƒ 
A Phillips-head screwdriver.
Note
If your installation requires CE Mark compliance, please refer to GFK-1179,
Installation Requirements for Conformance to Standards
, shipped with the PLC
programming software, for additional guidelines.
www.cadfamily.com    EMail:cadserv21@hotmail.com
The document is for study only,if tort to your rights,please inform us,we will delete