2.2.6 Update
Click the Update button to update the firmware installed on the selected F110. Updated 
firmware files provided by RLE, add new features and enhance the web browser interface. 
These firmware updates are available from RLE if firmware replacement is necessary.
Note
When obtaining the F110 Firmware Update file from the RLE Technologies website, be sure to 
save the file instead of opening it from a web browser. After receiving the file, right-click the 
F110 Firmware Update file and select “Properties.” If the F110 Firmware Update file has a “.zip” 
extension, replace “.zip” with “.upd” before uploading the file with the Device Discovery Utility.
2.3. F110 
Wiring
RLE recommends an 18AWG stranded copper wire for connection from each monitored point 
to the terminal block (TB) connection on the F110 (8 Switched Sensors inputs only). RLE 
recommends no more than 200 feet (60.9m) of wire at this specification. If longer runs are 
needed, please contact RLE for application guidance.
2.3.1 Power Supply
Plug the wall adapter into the connection labeled Power. The wall adapter has a 6 foot 
(18.82m) power cord. RLE recommends powering the F110 from a UPS supply to allow the 
F110 to send alarm notification during a power outage.
Figure 2.3 5VDC Power Supply Connection
NEVER connect main power to the sensors or sensor cables.
W
ARNING