Falcon MONITORING F110 ユーザーズマニュアル

ページ / 36
www.rletech.com
31
970.484.6510
A
P P E N D I X
C
HAPTER
 0
M
ODBUS
 R
EGISTERS
Table B.1 Read Output Registers
Register
Name
Description
Units
Range
40002
FC
Family Code (8 Switch Sensors)
None
0-65535
40003
SS
Switch Status (8 Switch Sensors)
None
0-65535
40004
SC
Current Alarm Setting (8 Switch Sensors)
None
0-65535
40005
AS
Current Alarm State (8 Switch Sensors)
None
0-65535
40009
FC
Family Code (External Sensor 1)
None
0-65535
40010
TC
Current Temperature (External Sensor 1)
Celsius x100 
0-65535
40011
TH
High Temperature (External Sensor 1)
Celsius x100
0-65535
40012
TL
Low Temperature (External Sensor 1)
Celsius x100
0-65535
40013
HC
Current Humidity (External Sensor 1)
% Relative Humidity
0-65535
40014
HH
High Humidity (External Sensor 1)
% Relative Humidity
0-65535
40015
HL
Low Humidity (External Sensor 1)
% Relative Humidity
0-65535
40016
FC
Family Code (External Sensor 2)
None
0-65535
40017
TC
Current Temperature (External Sensor 2)
Celsius x100 
0-65535
40018
TH
High Temperature (External Sensor 2)
Celsius x100
0-65535
40019
TL
Low Temperature (External Sensor 2)
Celsius x100
0-65535
40020
HC
Current Humidity (External Sensor 2)
% Relative Humidity
0-65535
40021
HH
High Humidity (External Sensor 2)
% Relative Humidity
0-65535
40022
HL
Low Humidity (External Sensor 2)
% Relative Humidity
0-65535
40023
FC
Family Code (External Sensor 3)
None
0-65535
40024
TC
Current Temperature (External Sensor 3)
Celsius x100 
0-65535
40025
TH
High Temperature (External Sensor 3)
Celsius x100
0-65535