Table 13-1
 MACHine Subsystem Parameter Values
Parameter
Value
arm_source 
{RUN | INTermodule | MACHine {1|2}}
pod_list
{NONE | <pod_num>[, <pod_num>]...}
pod_num
integer from 1 to 8
arm_level
integer from 1 to 11 representing sequence level
machine_name
string of up to 10 alphanumeric characters
res_id
{<state_terms>|H|J} 
for state analyzer
or
{<state_terms>|EDGE{1|2}}
 for timing analyzer
new_text
string of up to 8 alphanumeric characters
state_terms 
{A|B|C|D|E|F|G|I| RANGE{1|2}|TIMER{1|2}}
res_terms 
{<res_id>[,<res_id>]...}
MACHine 
Selector
:MACHine<N>
The MACHine <N> selector specifies which of the two analyzers (machines)
available in the Agilent 1670G-series logic analyzer which the commands or
queries will refer to.  Because the MACHine<N> command is a root level
command, it will normally appear as the first element of a compound header.
<N>
{1|2}
  (the machine number)
Example
OUTPUT XXX; ":MACHINE1:NAME ’TIMING’"
MACHine Subsystem
MACHine 
13–4