between propagations. If the update time is non zero, every update time ms a status SNVT is
scheduled for propagation. It is propagated even if the status has not been updated. If the update
time is zero then no propagation is scheduled on a timed interval. For a more detailed description
of the Status SNVT see Section 2.5.5.
Status SNVT Send on Update: This option schedules the status SNVT for propagation whenever
the SNVT is updated or the status changes. This is event driven and not time driven. For a more
detailed description of the status SNVT see Section 2.5.5.
Twin IP Address: This field displays/sets the redundant twin’s IP address
Twin IP Port: This field displays/sets the redundant twin’s IP port
709 Domain: These fields display the common domain address used for both the IP and LON
709.1 stacks.
Twin IP side Subnet/Node: This field displays the subnet/node address of the twin’s IP side 709.1
stack.
Twin LON CN side Subnet/Node: This field displays the subnet/node address of the twin’s LON
component network side 709.1 stack.
Twin Mode ON/OFF: These radio buttons turn twin mode on or off.
Trigger Twin App Service Pin: This button propagates a service pin message from the twin mode
monitoring application. This enables remote commissioning of the twin mode application.
Clear Twin LON CN Config: This button clears the component network configuration about its
twin from this device’s memory.
Sync Data From Twin: This button manually requests a sync packet from its twin.
Sync Data To Twin: This button manually sends a sync packet to its twin.
Submit Changes: This button updates the configuration memory of the device and refreshes the
web page to reflect any changes.