Duraflame Burner 61000 ユーザーズマニュアル

ページ / 20
-9-
IV. MINIMUM FIREBOX DIMENSIONS
WARNING: Maintain or exceed the minimum clearances.
V. CLEARANCES (Vent-free operation only)
WARNING: Maintain or exceed the minimum clearances.
VI. INSTALLING DAMPER STOP (Vented operation)
For vented operation of this appliance, a damper stop must be installed in the fireplace to prevent 
full closure of the damper blade.  The damper stop must be adjusted to provide a minimum flue 
opening of 29 square inches.  You can obtain a damper stop at your local hearth products dealer 
or hardware store.
WARNING: The fireplace and log set function as a system.  If the fireplace is spilling 
combustion gases into the room (check draft with a match, candle or smoke stick), reposition 
the damper clamp to open the damper wider, until a positive draft (i.e. all combustion 
emissions go up the chimney) is obtained.
VII. INSTALLATION
1.  Carefully remove the contents of the carton.  You should find:
  • The burner / base (Figure 1)
  • Four (4) ceramic fiber artificial logs (Figure 3).
  • Two (2) appliance base screws inside a small bag.
  • One AA battery.
  If components are missing, contact Duraflame Consumer Affairs.
2.  Remove all these components from their packaging.  When handling the logs, take care not 
to damage them.  Keep packing materials away from children, as they could be a choking or 
suffocation hazard.
Figure 2 
Minimum Dimensions of Firebox
Firebox Back
Firebox
Side
19”
18”
31”
15”