23
InstallatIon
Protection Zones
16.1  Terminals 13–24
Zones 1 to 8 (terminals 13 to 24) on the XR2500F panel are all grounded burglary zones. For programming
purposes, the zone numbers are 1 through 8. Listed below are terminal 13 to 24 connection functions.
Terminal
Function
Terminal
Function
13
Zone 1 voltage sensing
19
Zone 5 voltage sensing
14
Ground for Zones 1 and 2
20
Ground for Zones 5 and 6
15
Zone 2 voltage sensing
21
Zone 6 voltage sensing
16
Zone 3 voltage sensing
22
Zone 7 voltage sensing
17
Ground for Zones 3 and 4
23
Ground for Zones 7 and 8
18
Zone 4 voltage sensing
24
Zone 8 voltage sensing
Note: Zones 1 and 2 have been pre-wired to the two 866 NAC modules. All other zones are available.
The voltage sensing terminal measures the voltage across a 1k Ohm End-of-Line resistor to ground. Use
DMP Model 311 1k Ohm resistors. Dry contact sensing devices can be used in series (normally-closed) or in
parallel (normally-open) with any of the burglary protection zones.
1K Ohm
Normally
Closed
1K Ohm
Normally Open
1K Ohm
Combination Normally Open
and Normally Closed
Figure 12: Protection Zone Wiring
16.2  Operational Parameters
Each protection zone detects three conditions: Open, Normal, and Short. Listed below are voltage and
resistance parameters for each condition:
 
   
Condition   
Resistance on zone   
Voltage on zone terminal
Open
over 1300 Ohms
over 2.0 VDC
Normal
600 to 1300 Ohms
1.2 to 2.0 VDC
Short
under 600 Ohms
under 1.2 VDC
16.3  Zone Response Time
A condition must be present on a zone for 500 milliseconds before it is detected by the XR2500F panel.
Ensure detection devices used on the protec tion zones are rated for use with this delay. Zones 1-10 can also
be programmed for a fast response delay of 160 milliseconds.
16.4  Keyswitch Arming Zone
Using a keyswitch on an Arming type zone allows you to arm and disarm selected areas without having to
enter a user code.