Delta Timer/Counter/Tachometer CTA プリント

ページ / 2
 
2006-12-08
5011646001-CTE1
 
   
 
Instruction Sheet 
Thank you very much for purchasing DELTA CTA series. Please read this instruction sheet before using your CTA 
series to ensure proper operation and please keep this instruction sheet handy for quick reference. 
 
¾
 
DANGER! Caution! Electric Shock! 
¾
 
When the power is on, DO NOT touch the AC terminals in case an electric shock may occur. 
¾
 
Make sure the power is disconnected when you check the unit inside. 
 
¾
 
CTA series is an OPEN-TYPE device. They are intended for installation completely within an overall panel and are for use 
in counting or timing application. If it will cause serious injury to workers or damage on other equipments when used in a 
dangerous environment, please make sure it is installed in an automatic safety protection device. 
1.
 
 
  
Precaution
 
1.  Always use recommended solder-less terminals: Fork terminal with isolation (M3 screw, width 7.0mm), hole (diameter 
3.2mm). Screw size: M3x6.5 (with 6.8x6.8 square washer). Recommended tightening torque: 0.4 N.m (4kgf.cm). 
Applicable wire: solid/twisted wire of 2mm
2
, 12AWG to 24 AWG. Please be sure to tighten them properly. 
2.  Prevent dust or metallic debris from falling into the device and cause malfunctions. 
3.  DO NOT modify or uninstall the device. 
4.  DO NOT use empty terminals. 
5.  Make sure the wires are correctly connected to proper terminals. 
6.  Keep away from high-voltage and high-frequency environment during installation in case of interference. 
7.  Prevent using the device in premises which contain: 
Dust or corrosive gas    ․High humidity    ․High radiation    ․Vibration and shock 
8.  CTA series is an open-type device. Make sure to install it in an enclosure to prevent dust, humidity in case of an electric 
shock. 
9.  Please make sure the power cables and signal device are installed correctly before switching on the power; otherwise 
serious damage may occur.。 
10.  DO NOT touch the terminals or repair the device when the power is on; otherwise an electric shock may occur. 
11.  Please wait for one minute after the power is switched off to allow the capacitor to discharge and DO NOT touch the 
internal wiring within this period. 
12.  Use dry cloth to clean the device. DO NOT use acid or alkaline liquid to clean the device. 
2.
 
Display, Indicators and Keys
 
Reset 2 indicator
Reset 1 indicator
Key protect 2 indicator
Output 2 indicator
Key protect 1 indicator
Output 1 indicator
Special function indicator
Lock key
Reset key
Mode and number shift key
PV(Present Value) display
SV(Set Value) display
Timer function indicator
Counter function indicator
Tachometer function indicator
Up/Down key
 
 
™
 
LCD Display and indicators 
RST 1/2  Light on when reset signal is detected 
BATCH  “Batch Counting Mode” in Counter and Tachometer function 
K/P 1/2  Light on when key-protected mode is enabled SET 1 2  SV1, SV2 display 
OUT 1/2  Light on when output is executing 
TAC  Light on when Tachometer function is executing 
H M S  Hour, minute, second, unit of timer, displayed 
in Timer function 
CNT  Light on when Counter function is executing 
TOTAL  “Total Counting Mode” in Counter and 
Tachometer function 
TMR  Light on when Timer function is executing 
™
 
Key Operation
 
  Increase and decrease SV or change parameter settings. 
  Left move 1 digit of the selected digit. The indicator of the selected digit will flash. 
MODE
  Save the set parameters or switch among functions. 
LOCK 
Prevent settings from being changed. Key-protected mode still works after the power is switched off. Press 
LOCK
 to enter key-protected mode. In non-key-protected status, press 
LOCK
 to enter Lock 1. In Lock 1, press 
LOCK
 again to enter Lock 2. Press
MODE
and
at the same time to disable key-protected mode. 
(Lock 1) 
disables the functions of all keys. 
(Lock 2) allows users to change SV and functions of 
RESET
 remain. 
LOCK
 only functions in non-key-protected status. 
RESET 
Clear and reset PV. 
™
 
Modes: Operation Mode and Configuration Mode
 
Operation  When the power is on, the timer/counter/tachometer is in the operation mode. Press
to change SV, or 
to make change on a desired digit. The indicator of the selected digit will flash. After the change is made, 
press
MODE
to save the setting. If SV or parameters are not changed, press
MODE
once to switch between SET1 and 
SET2. 
Configuration  Press
MODE
  in operation mode for more than 3 seconds to enter configuration mode. Press
MODE
once to switch 
among parameters. To return to operation mode, press
MODE
for more than 3 seconds. 
3.
 
Ordering Information
 
CTA
2
3
4
5
6
1
 
n
 Product name  CTA: Delta Counter/Timer/Tachometer A series  q Preset stage 
0: 2 preset stage 
o
 Panel size 
4: 48mm x 48mm 1/16DIN 
r
 Communication  0: none 
p
 Output 2 
0: NPN; 1: Relay 
s
 Power supply A: 
AC 
100~240V 
4.
 
 
  
Specification 
Power input   AC 100~240V, 50/60Hz 
Input voltage range   85% to 110%, rated voltage 
Power consumption   Less than 10VA 
External power supply   12Vdc ±10%, 100mA 
Display    Double-line, 6-digit negative transmissive LCD display 
Non-voltage input (NPN): ON impedance 1K ohm max. ON residual voltage: 2V max. 
Input signal  
Voltage input (PNP): High level: 4.5 to 30Vdc, Low level: 0 to 2Vdc 
Relay: SPST max.250Vac, 5A (resistance load) 
Output 1  
Transistor: NPN open collector. When 100mA /30Vdc, residual voltage=1.5Vdc max. 
Relay: SPDT max.250Vac, 5A (resistance load) 
Output 2  
Transistor: NPN open collector. When 100mA /30Vdc, residual voltage=1.5Vdc max. 
Dielectric strength   2000Vac 50/60 Hz for 1 minute 
Vibration resistance   Without damage: 10~55Hz, amplitude=0.75mm, 3 axes for 2 hours 
Shock resistance   Without damage: drop 4 times, 300m/s
2
, 3 edges, 6 surfaces and 1 corner 
Ambient temperature   0 
o
C to +50 
o
Storage temperature   -20 
o
C to +65 
o
Altitude    2000m or less 
Ambient humidity   35% to 85% RH (non-condensing) 
Pollution degree   Degree 2 
5.
 
 
  
Parameters in Configuration Mode 
™
 
Timer 
 
Select a 
function 
 
 
 
MODE
 
 
Setup Timer 
function, 
(counting up 
or down) 
 
MODE
 
 
Select 
output 
mode of 
Timer 
 
MODE
 
 
Setup the 
displayed 
unit of timer 
 
 
MODE
 
 
Setup the 
pulse width 
of output 1 
 
 
MODE
 
 
Reset min. 
pulse width 
 
 
 
MODE
 
 
Select input 
type (PNP 
or NPN)   
 
 
MODE
 
Back to 
“select a 
function” 
™
 
Counter 
   
Select a 
function 
 
 
MODE
 
 
Select 
counting 
modes 
 
MODE
 
 
Setup input 
mode of 
Counter 
 
MODE
 
 
Setup output 
mode of 
Counter (not 
dual output) 
MODE
 
 
Setup dual 
output counting 
mode (dual 
output) 
MODE
 
 
Setup counting 
speed 
 
 
MODE
 
 
Setup the 
pulse width of 
output 1 
 
MODE
 
Back to 
“select a 
function” 
 
Select input 
type (PNP or 
NPN) 
 
MODE
 
 
Reset min. 
pulse width 
 
 
MODE
 
 
Save data or 
not while 
switching off 
power 
MODE
 
 
Setup pre-scale 
value 
 
 
MODE
 
 
Setup the 
decimal point 
 
 
MODE
 
 
Setup the 
pulse width of 
output 2 
 
MODE
 
™
 
Tachometer 
   
Select a function 
 
 
MODE
 
 
Setup output mode 
of Tachometer 
 
MODE
 
 
Setup counting 
speed 
 
MODE
 
 
Setup the decimal 
point 
 
MODE
 
 
Setup pre-scale value 
 
 
MODE
 
Back to “select a 
function”
 
 
Select input type 
(PNP or NPN) 
 
MODE
 
 
Reset min. pulse 
width 
 
MODE
 
!
Setup the average of 
input data 
 
MODE
 
 
Setup the delay time 
while switching on 
power 
MODE
 
™
 
Timer + Counter Mixed 
 
Select a 
function 
 
 
 
MODE
 
 
Setup Timer 
function, 
(counting 
up or down) 
 
MODE
 
 
Setup 
output 
mode of   
timer 
 
MODE
 
 
Setup the 
displayed 
unit of 
timer 
 
MODE
 
 
Setup 
input 
mode of 
Counter 
 
MODE
 
 
Setup 
output 
mode of 
Counter (not 
dual output) 
MODE
 
 
Setup 
counting 
speed 
 
 
MODE
 
 
Setup the 
pulse width 
of output 1 
 
 
MODE
 
 
Back to 
“select a 
function”
 
 
Select 
input type 
(PNP or 
NPN) 
 
MODE
 
 
Reset 
min. 
pulse 
width 
 
MODE
 
 
Save data 
or not 
while 
switching 
off power 
MODE
 
 
Setup 
pre-scale 
value 
 
 
MODE
 
 
Setup 
the 
decimal 
point 
 
MODE
 
 
Setup the 
pulse 
width of 
output 2 
 
MODE
 
6.
 
 
  
Timer Function 
There are counting up/down modes, several counting units and output modes to choose from in timer function. 
 
 
Select counting up
  or counting down
 
 
Setup the output time of timer, from 0 to 99.99 secs. 0= Hold output 
 
Setup output modes 
 
 Setup the counting unit of the timer. 
 
 sec 0.01~9999.99 
 A unit = 10ms. 
Max. counting = 9999.99 secs. 
 
 sec 0.1~99999.9 
 A unit = 0.1sec. 
Max. counting = 99999.9 secs. 
 
 sec 1~999999 
 A unit = 1 sec. 
Max. counting = 999999 secs. 
 
 min,sec 0.01~9959.99 
 A unit = 0.01 sec.  Max. counting = 5999.99 secs. 
 
 min,sec 0.1~99959.9 
 A unit = 0.1 sec. 
Max. counting = 59999.9 secs. 
 
 min 0.1~99999.9 
 A unit = 0.1 min. 
Max. counting = 99999.9 mins. 
 
 min 1~999999 
 A unit = 1 min. 
Max. counting = 999999 mins. 
 
 hr,min,sec 1~995959 
 A unit = 1 sec. 
Max. counting = 359999 secs (100hr) 
 
 hr,min 1~999959 
 A unit = 1 min. 
Max. counting = 35999999 secs (10000hr) 
 
 hr 1~999999 
 A unit = 1 hr. 
Max. counting = 999999 hrs 
 
Power signal
Start signal
Pause signal
Clear signal
Up
Down
0
0
SV
SV
Signal On Delay 1
t
t
Output signal
 
 
Power signal
Start signal
Pause signal
Clear signal
Output signal
Up
Down
0
0
SV
SV
Signal On Delay 2
t
t
 
 
Power signal
Start  signal
Pause  signal
Clear  signal
Output  signal
SV
0
Up
Down
SV
0
Signal Off Delay
 
 
Power signal
Start signal
Pause signal
Clear signal
Output signal
SV
0
Up
Down
SV
0
Signal On
 
 
Power signal
Start signal
Pause signal
Clear signal
Output signal
Up
Down
SV
SV
0
0
Power On Delay
t
t
t
 
 
Power signal
Start signal
Pause signal
Clear signal
Output signal
Up
Down
SV
SV
0
0
Power On Delay Hold
t
t
t
t
 
 
Power signal
Start signal
Pause signal
Clear signal
Output signal
Up
Down
SV
SV
Repeat Cycle
0
0
timer output set as 0
 
 
Power signal
Start signal
Pause signal
Clear signal
Output signal
Up
Down
 
SV
 
SV
 
Repeat Cycle
t
t
t
 
timer output not set as 0
 
 
Power signal
Start signal
Pause signal
Clear signal
Output signal
Up
Down
SV
SV
0
0
Repeat Cycle Hold
Timer output set as 0
 
 
Power signal
Start signal
Pause signal
Clear signal
Output signal
Up
Down
SV
SV
0
0
RCYH timer output not set as 0
t
t
t
 
 
Power signal
Start signal
Pause signal
Clear signal
Output signal
Up
Down
SV1
SV1
SV2
SV2
0
0
Repeat Cycle 2
 
 
Power signal
Start signal
Pause signal
Clear signal
Output signal
Up
Down
0
SV
SV
0
Signal Cumulate
 
 
Power signal
Start signal
Pause signal
Clear signal
Output signal
Up
Down
SV1
SV2
SV1
0
0
SV2
Signal Twin ON-Start
 
 
Power signal
Start signal
Pause signal
Clear signal
Output signal
Up
Down
SV1
SV1
SV2
SV2
0
0
Signal Twin OFF-Start