Bryan Boilers CLM-120-WT-FDG-844-AV-CM-IN ユーザーズマニュアル

ページ / 4
Bryan Water-Pak
TM
 Indirect Water Heater Systems
Specifications subject to change without notice.
Contact factory to consult on other boiler options.
Form No. 2300                                                                                                                                      ©2004 Bryan Steam LLC                                                                                                                   
 Printed in USA
 54-5368
Indirect Heater Specifications
Heater
Model
Output
Series
Number
BTU/HR 80°-140° 60°-140° 40°-140° 40°-160°
DR SERIES
DR/F-350-WT
280,000
559
420
336
(Forced Draft)
DR/F-450-WT
360,000
720
540
432
F SERIES
DR/F-650-WT
520,000
1,039
780
624
(Atmospheric)
DR/F-850-WT
680,000
1,359
1,020
816
CLM SERIES
CLM-120-WT
960,000
1,920
1,440
1,152
960
(Forced Draft)
CLM-150-WT 1,200,000
2,400
1,800
1,440
1,200
&
CLM-180-WT 1,440,000
2,880
2,160
1,728
1,440
(Atmospheric)
CLM-210-WT 1,680,000
3,660
2,520
2,016
1,680
CLM-240-WT 1,920,000
3,840
2,880
2,304
1,920
CLM-270-WT 2,160,000
4,320
3,240
2,592
2,160
CLM-300-WT 2,400,000
4,800
3,600
2,880
2,400
K SERIES
K-350-WT
2,800,000
5,600
4,200
3,360
2,800
(Atmospheric)
K-400-WT
3,200,000
6,400
4,800
3,840
3,200
K-450-WT
3,600,000
7,200
5,400
4,320
3,600
K-500-WT †
4,000,000
8,000
6,000
4,800
4,000
K-550-WT †
4,400,000
8,800
6,600
5,280
4,400
K-600-WT †
4,800,000
9,600
7,200
5,760
4,800
K-650-WT †
5,200,000 10,400
7,800
6,240
5,200
AB SERIES
AB-90-WT
720,000
1,440
1,080
864
720
(Forced Draft)
AB-120-WT
960,000
1,920
1,440
1,152
960
AB-150-WT
1,200,000
2,400
1,800
1,440
1,200
AB-200-WT
1,680,000
3,360
2,520
2,016
1,680
AB-250-WT
2,000,000
4,000
3,000
2,400
1,999
AB-300-WT
2,400,000
4,800
3,600
2,880
2,400
RV SERIES
RV-350-WT
2,800,000
5,600
4,200
3,360
2,800
(Forced Draft)
RV-400-WT
3,200,000
6,400
4,800
3,840
3,200
RV-450-WT
3,600,000
7,200
5,400
4,320
3,600
RV-500-WT †
4,000,000
8,000
6,000
4,800
4,000
RV-550-WT †
4,400,000
8,800
6,600
4,280
4,400
RV-600-WT †
4,800,000
9,600
7,200
5,760
4,800
RV-700-WT †
5,600,000 11,200
8,400
6,720
5,600
RV-800-WT †
6,400,000 12,800
9,600
7,680
6,400
Bryan Steam LLC — Leaders Since 1916
783 N. Chili Ave., Peru, Indiana 46970 U.S.A.
Phone:765-473-6651  • Internet: www.bryanboilers.com
Fax: 765-473-3074  • E-mail: bryanboilers@iquest.net
Water-Pak Selection
Water-Pak units are built to furnish a very wide selection of
recovery rates, storage capacities and configurations. Both
horizontal and vertical tanks are available to best fit into the
space allocation. In addition to the combinations of "settings"
shown below, other combinations, arrangements and sizes
are possible. Fuel selection includes gas (atmospheric or
forced draft), oil, gas-oil or electric (consult factory).
1. Select Heater Model based on "Heater Specifications" table
below.
2. Select storage capacity from "Storage Tank Specifications"
tables, horizontal or vertical tank depending on space
considerations.
3. Choose appropriate "Setting" from "Heater, Tank Setting"
diagrams on previous page.
Selection Procedure Example
A requirement of 800 gph at 100° rise. Storage capacity 1000
gallons. Fuel, gas. Tank lining, cement.
1. From "Heater Specifications" table, select Model No. CLM-
120-WT Gas, rated at 1,152 gph, 40° to 140° rise.
2. From the  "Storage Tank Specifications" tables, suppose
you select the 1045 gallon horizontal tank.
3. Then the setting shown in diagram "AH" (horizontal tank)
would be appropriate.
Specify:
Specify:
Specify:
Specify:
Specify:
Water-Pak System CLM-120-WT - G - 1045 - AH - CM - IN
Storage Tank Specifications
Tank
Tank
Approximate
Capacity
Dia × Length
Weight
gallons
in (cm)
lbs (Kg)
Horizontal Tanks
H-387
36×96 (91.4×243.8)
2,000 (907)
H-520
42×96 (106.7×243.8)
2,200 (998)
H-802
42×144 (106.7×365.8)
3,000 (1,361)
H-1045
48×144 (121.9×365.8)
3,800 (1,724)
H-1546
54×168 (137.2×426.7)
5,600 (2,540)
H-2188
60×192 (152.4×487.7)
6,900 (3,130)
H-2699
72×168 (182.9×426.7)
8,100 (3,674)
H-3533
72×216 (182.9×548.6)
10,100 (4,581)
Vertical Tanks
V-335
36×84 (91.40×213.4)
1,700 (771)
V-520
42×96 (106.7×243.8)
2,200 (998)
V-665
48×96 (121.9×243.8)
2,700 (1,225)
V-844
54×96 (137.2×243.8)
3,100 (1,406)
V-1030
60×96 (152.4×243.8)
4,000 (1,814)
V-1447
72×96 (182.9×243.8)
5,300 (2,404)
V-1922
84×96 (213.4×243.8)
7,000 (3,175)
Fuel
Fuel
Fuel
Fuel
Fuel
G—gas
O—oil
GO—gas-oil
Storage
Storage
Storage
Storage
Storage
Section
Section
Section
Section
Section
Size
Size
Size
Size
Size
(gals.)
Tank
Tank
Tank
Tank
Tank
Insulated
Insulated
Insulated
Insulated
Insulated
PVC
PVC
PVC
PVC
PVC
Jacket
Jacket
Jacket
Jacket
Jacket
Indirect
Indirect
Indirect
Indirect
Indirect
Heater
Heater
Heater
Heater
Heater
Model
Model
Model
Model
Model
Setting
Setting
Setting
Setting
Setting
Tank Lining
Tank Lining
Tank Lining
Tank Lining
Tank Lining
CM—cement
PH—phenolic
Gallons Per Hour*
Heater Capacity
† These units are equipped with two heat exchangers as standard and require a copper header to be field supplied.
*
Note 1: Contact factory for ratings at other conditions.
Note 2: Heater is not intended to provide the temperature increases shown above instantly, but will raise the
temperature of the gallons listed to final storage temperature within one hour.
Note 3: Select adequate storage tank capacity to handle peak demand. Keep in mind that, typically, only 75%
of tank capacity is usable storage.