Bryan Boilers CLM Series ユーザーズマニュアル

ページ / 4
Low initial cost, high operating efficiency
deliver substantial return on investment
and inspection, front and rear openings, upper and lower
drums.
L. Steam boilers with extra large drum with high steam
release area ensure stable water level and dry steam.
M. Steel plate boiler base with lightweight, high tempera-
ture insulating firebrick combustion chamber, designed
for maximum combustion efficiency.
Quality Construction Features
A. Heavy steel boiler frame, built and stamped in accor-
dance with the appropriate ASME Boiler Code.
B. Large volume water leg downcomers promote  rapid
internal circulation, temperature equalization and efficient
heat transfer.
C. Bryan bent water tubes are flexible, individually re-
placeable without welding or rolling. Never more than two
tube configurations.
D.  Boiler tube and furnace area access panel: heavy
gauge steel casing with 2" high temperature ceramic fiber
and insulation, bolted and tightly sealed to boiler frame.
E. Jacket access panels make the interior of the boiler
easily accessible for service and inspection.
F. Heavy gauge steel boiler jacket with rust-resistant zinc
coating and attractive enamel finish, insulated with 1½"
fiberglass to insure exceptionally cool outer surface.
G. Minimum sized flue vent.
H. Forced draft, flame retention head type burner. Effi-
cient combustion of oil or gas, quiet operation.
I. All controls, gauges, relief valve(s) are factory installed
and wired and easily accessible for servicing.
J. Electrical box: all controls installed and connected to
terminal strip.
K. Water side or steam side interior accessible for cleanout
True “flexible water tube”
design guaranteed shock free
Longer service life with
superior performance
Full five sq ft of heating
surface per BHP
Water Boiler
Combination thermometer and pres-
sure gauge, ASME-rated boiler relief
valve, water temperature control (240°F
max std.), high limit control, probe
LWCO.
Steam Boiler
Steam pressure gauge, steam pres-
sure control, combination low water
cutoff and pump control, auxiliary low
water cutoff, high limit pressure con-
trol, ASME-rated boiler relief valve,
water glass set.
Straight gas fired unit
Electronic combustion safety control,
automatic operating gas valve, safety
gas valve, pilot solenoid valve, pilot
ignition assembly, main manual gas
shut-off valve, pilot cock, pilot and
main gas pressure regulators, air safety
OPTIONAL EQUIPMENT:
1. Manual reset high limit control
2. Manual reset low water cutoff
3. Auxiliary low water cutoff
4.  Combination low water cutoff
and feeder
5. Alarm bells or horns
6. UL, CUL, CSD-1, FM, IRI or
other insur-ance approved
control systems
7. Control panel mounted on boiler
8. Indicating lights, as desired
9. Lead-lag systems for two or
more boilers with or without
outdoor reset control
10. Draft control system
11. Special construction: left hand,
Knocked Down.
OPTIONAL CONSTRUCTION:
When ordering, please specify:
1. Boiler size
2. Supply and return tempera-
tures required
3. Boiler relief valve setting
4. Type of fuel: natural, LP, or
other gas and/or No. 2 oil
5. If gas, type, BTU content,
specific gravity and pressure
available
6. Electric power voltage, phase
and frequency
7. Optional extra equipment or
construction
8. Special approvals required
(UL, CUL, CSD-1, FM, or IRI)
9. Altitude
Steam boiler
Optional construction to ASME Power
Boiler Code requirements for pressure
exceeding 150 psi to maximum of 300
psi design pressure.
Hot water boiler
Optional construction to ASME Power
Boiler Code requirements for tempera-
tures exceeding 240° F and/or pressure
exceeding 160 psi to maximum of 285°
F operating and 300° F  design tempera-
ture and 250 psi.
Bryan CLM Series Boilers Standard and Optional Equipment
STANDARD EQUIPMENT FURNISHED
switch, control panel, all controls in-
stalled and wired.
Straight oil fired unit
Electronic combustion safety control,
dual oil valves, oil ignition transformer,
two-stage fuel unit, direct spark
ignition of oil, oil nozzle assembly,
control panel, all controls installed
and wired.
Combination gas-oil unit
Electronic combustion safety control,
automatic operating gas valve, safety
gas valve, pilot solenoid valve, pilot
ignition assembly, main manual gas
shut-off valve, pilot cock, pilot and
main gas pressure regulators, air
safety switch, manual fuel selector
switch, dual oil valves, gas pilot for
both fuels,   two-stage fuel unit,  nozzle
assembly, control panel, all controls
installed and wired.
A
G
B
C
K
J
D
I
E
H
L
F
M