Bryan Boilers & 300 ユーザーズマニュアル

ページ / 81
 
Date:  
8-4-2010 
 
Revision: 0 
 
Form:  
2396
 
WARNING: 
Improper servicing and start-up of this 
equipment may create a potential 
hazard to equipment, operators, or 
persons in the building. 
Only fully trained and qualified 
personnel should do servicing and 
start-up. 
 
WARNING: 
Before disconnecting or opening any 
fuel line, cleaning or replacing parts of 
any kind take the following 
precautions. 
Turn OFF the main fuel shutoff valves, 
including the pilot gas cock if 
applicable. 
Turn OFF all of the electrical 
disconnects to the burner, boiler and 
any other equipment or systems 
electrically interlocked with the burner 
or boiler. 
All cover plates, enclosures, and 
guards must be in place at all times 
except during maintenance and 
servicing.                                                                                                                
 
2.1 B
OILER 
A
SSEMBLY
 
The Triple-Flex boiler is a fully integrated 
assembly consisting of a Metal Fiber Pre-Mix 
Burner Head and the necessary fittings, valves, 
and safety devices.  The boiler equipment list 
provided in the boiler manual lists the 
components supplied for the boiler assembly.  
Refer to the boiler dimensional for location 
dimensions.  A description of the major 
components follows.  For additional information 
refer to the manufactures literature provided in 
the boiler manual. 
2.1.1 T
RIPLE
-F
LEX 
F
RONT 
V
IEW
 
 
Figure 3 Triple-Flex Front View 
 
1. The boiler cabinet door provides easy 
access to boiler and burner components.  
This door should remain closed during 
normal operation to ensure proper flow of air 
around the boiler flue collector. 
2.  The boiler supply water connection provides 
heated water to the system.  This 
connection is a standard ANSI 150# class 3” 
flange. 
3.  The boiler water pressure gauge is 2” 
diameter and will have a range not less than 
1-1/2 nor more than 3-1/2 times the 
pressure setting of the boiler safety relief 
valve. 
4.  The boiler water temperature gauge is 2” 
diameter and is located so that it will indicate 
the boiler water temperature at the supply 
water connection of the boiler. 
5.  The boiler touch panel display provides a 
human interface for controlling the boiler.  
Controlling the boiler with the touch panel 
display will be explained in section 2.2. 
11 
 
6.  The boiler on / off switch will turn on or off 
the 120 volt ac control voltage for every 
electrically connected device.  This includes