Bryan Boilers & 300 ユーザーズマニュアル

ページ / 81
 
Date:  
8-4-2010 
 
Revision: 0 
 
Form:  
2396
 
2.2.21 C
ENTRAL 
H
EAT 
C
ONFIGURATION
 
► ► CONFIGURE 
► CH - CENTRAL HEAT 
CONFIGURATION 
 
Figure 36 Central Heat Configuration (Central Heat Page) 
 
CH enable 
 
Disable or Enable Central 
Heating Loop
 
Demand switch 
 
Sensor for Central Heat 
demand: 
 
Sensor only 
Sensor & STAT terminal 
Sensor & Remote Stat 
LCI & Sensor
 
Outdoor reset
 
Enabled 
Disabled
 
CH has priority over Lead 
Lag
 
Yes, No, Cancel
 
 
 
 
Figure 37 Central Heat Configuration (Setpoint Page) 
 
Setpoint source
 
Local 
S2 (J8-6) 4-20mA
 
Setpoint
 
Setpoint for normal 
Central Heat modulation: 
50 °F to 190 °F
 
Time of day setpoint
 
Setpoint when Time Of 
Day switch is on. 50 °F to 
190 °F
 
Off hysteresis
 
Differential above 
setpoint when boiler is 
turned off. 2 °F to 5 °F
 
On hysteresis
 
Differential from setpoint 
when boiler is turned on. 
2 °F to 30 °F
 
4 mA water temperature
 
50 °F to 190 °F
 
20 mA water temperature
 
50 °F to 190 °F
 
 
 
Figure 38 Central Heat Configuration (Modulation Page) 
 
Modulation sensor 
 
Outlet sensor, Inlet 
sensor, S5 (J8-11)
 
Modulation Rate Source
 
Local
 
P-gain Gain
 
applied for the P portion 
of the PID equation 0-400
I-gain Gain
 
applied for the I portion of 
the PID equation 0-400
 
D-gain
 
Gain applied for the D 
portion of the PID 
equation 0-400
 
Hysteresis step time 
(0=Disable hysteresis 
stepping)
 
Time between hysteresis 
step changes: 0-600 
seconds
 
 
2.2.22 S
OUND 
P
RESSURE 
L
EVELS
 
Sound pressure levels were measured at 4-1/2’ 
above the floor and 3’ from the boiler at the 
front, rear and two sides.  See Table 6 for 
decibel readings. 
 
27 
 
 Decibel 
Readings 
Model Front  Rear 
Tube 
Side 
Right 
Side