WARNING: 
During pilot adjustment leave the 
manual main gas cock (Figure 7 item 
4) closed. 
 
NOTE: 
Pilot gas pressures in excess of the 
recommended will lead to the formation of 
carbon hairs that will ground out the pilot igniter 
causing a safety shutdown. 
 
2.3.6 I
NITIAL 
L
IGHT 
O
FF
 
Open the manual main gas cock (Figure 7 item 
4).  Clear the lockout fault (paragraph 2.2.10) 
and allow the burner to cycle and attempt to light 
off.  If the main flame fails to light, the low fire 
displacement of the pressure regulating actuator 
(Figure 7 item 2) may need to be increased. 
 
WARNING: 
Do not adjust the low fire displacement 
more than 1/4 to 1/2 turn for each main 
flame-establishing period. 
The boiler will light off at approximately 1.5 times 
the minimum firing rate rpm.  The boiler will hold 
in this position for no less than 5 minutes to 
establish a stable flame before releasing the 
boiler to full modulation.  Observe combustion 
readings and make small adjustments to the low 
fire displacement of the pressure regulating 
actuator (Figure 7 item 2) when the O2 is not 
within 6% to 10%.  Allow sufficient time for 
combustion to stabilize after each ¼ to ½ turn of 
the low fire displacement (Figure 7 item 2). 
2.3.7 A
DJUSTING 
B
OILER 
M
AXIMUM 
I
NPUT
 
After the flame stabilization period increase the 
firing rate in 500 rpm increments until the 
maximum modulation rate (paragraph 2.2.13) i
reached.  For each 500 rpm increment observe 
combustion readings and make adjustments to 
the gas limiting orifice (Figure 7 item 26) if the 
O2 is not within 6% to 10%.  Final adjustments 
for NOx, O2, and CO should be made at the 
maximum firing rate.  No further adjustments are 
required of the gas limiting orifice valve.  Return 
to the minimum low fire rate (paragraph 2.2.13) 
in increments of 500 rpm.  For each increment 
verify combustion readings.  Refer to trouble 
shooting (paragraph 0) for further help. 
 
NOTE: 
Use rpm values that fall between the rpm values 
used going to high fire.  This will give more 
points to verify on the modulation curve. 
2.3.8 A
DJUSTING 
B
OILER 
M
INIMUM 
I
NPUT
 
NOTE: 
The boiler maximum input must be adjusted 
before final adjustments can be made for 
minimum input. 
 
Decrease the boiler firing rate to the minimum 
modulation rate (paragraph 2.2.13).  Adjust the 
O2 level to obtain Nox levels desired by 
adjusting the low fire displacement on the gas 
pressure regulating actuator to obtain 
appropriate NOx, O2, and CO levels.  Allow 
sufficient time for combustion to stabilize after 
each ¼ to ½ turn of the low fire displacement 
(Figure 7 item 2). 
 
WARNING: 
O2 levels below 6% will overheat the 
metal fiber burner and cause the fuel / 
air mixture to ignite inside the burner.  
An internal temperature fuse is 
provided to open when the internal 
burner temperature reaches 425 
o
F. 
37 
 
Boiler Model 
TF300 TF250 TF200 TF150 
 
 
 
 
 
Pilot Gas 
Pressure 
(IWC) 
3.5 - 4  3.5 - 4  3.5 - 4  3.5 - 4 
Light Off 
RPM 
1800 1800 1200 1200 
High Fire