Bryan Boilers & 300 ユーザーズマニュアル

ページ / 81
 
Date:  
8-4-2010 
 
Revision: 0 
 
Form:  
2396
 
 
4.4 L
EAD
-L
AG 
O
PERATION
 
This is a summary of the functional capability of 
the embedded lead-lag on the Sola control. 
OEM Configurable parameters may be adjusted 
as part of the OEM factory configuration and in 
the field using the System Display with 
appropriate password permissions. Specific 
parameters may also be configured in the field 
by the local display 1.  Field Installation 
Configuration a. The master and slave 
controllers are enabled via the S7910 or S7999 
display. b. All Sola controllers are programmed 
with a default address of 1. Assuming the 
Master Sola controller remains address 1, the 
address of the slave controllers in the system 
must have a unique address (1..8) via the local 
display.  2.  Basic Operation a. Firing rate 
determination – Parallel common-base limited 
(1) All boilers have a single assignable base 
load firing rate. (2) Allocation (a)As load 
increases: (i) Until all stages are Firing - No 
stage is requested to exceed the common base 
load rate. (ii)After all stages are Firing - There is 
no restriction on the slave's commanded firing 
rate. (b)As load decreases: (i) As long as all 
available stages are firing - There is no 
restriction on the slave's commanded firing rate. 
(ii)When at least one stage has been dropped - 
No stage is requested to exceed the common 
base load rate. b. Rotation (1) The lead boiler is 
rotated based sequence order. The lead boiler 
rotation time is a configurable OEM assigned 
parameter. Rotation is sequential by address (1-
2-3-4; 2-3-4-1; etc.) (2) Rotation trigger occurs at 
the start of each new heat cycle. c. Source of 
heat for call – The call for heat originates at the 
master boiler. This source may be configured to 
be an external thermostat or via EnviraCOM 
Remote Stat. d. Slave boiler lockout – If any 
slave is in lockout the master boiler will cause it 
to be skipped and all system load setting 
calculation settings will be based only on 
available boilers. e. Master boiler lockout – If the 
master boiler is in lockout then its burner control 
function will be skipped in the rotation the same 
as the slave controllers. However, the master 
boiler function will continue to operate. 3. 
System Component Failure Responses a. If the 
system header sensor becomes disconnected 
from the master boiler then the master boiler will 
control off of one of the following OEM 
configurable actions (1) Disable - No backup will 
be used (a)Lead Outlet - Outlet temperature of 
the lead boiler will be used as the backup during 
firing (i) Slave Outlet Average - Average of the 
outlet temperatures of all slave boilers that are 
firing will be used as a backup (b) If the sensor 
chosen by the above parameter is faulty then 
the backup sensor provided may be used. When 
burner demand is off and no burners are firing 
then, for either "Lead Outlet" or "Slave Outlet 
Average", the lead boiler's outlet temperature is 
used to monitor for burner demand. 4.  Local 
Display Configuration and Operation a. The 
configuration parameters available on the local 
display are edited in the Service Mode b. Access 
to the Service Mode is accomplished by 
pressing both up/down buttons for 3 seconds. c. 
Status and Operation (1) Slave status (a) “Rmt” 
and “Adr” icons are on to show slave (follower) 
has been enabled. (b)Current burner status is 
shown (c) To show slave CFH (i) Alternate “%” 
firing rate and actual (slave) Outlet temp to 
indicate slave CFH otherwise show the Home 
screen. (2) Master status (a)Rmt icon is on, Adr 
icon is off to show Master (Leader) has been 
enabled. (b)Current burner status is shown (c) 
Actual temperature LL (Header) temperature is 
shown as described in 4e below. (d)Pressing the 
up/down buttons allows setpoint adjustment for 
LL-CH only (not LL-DHW or LL-Mix or others). (i) 
All pump configurations must be done using the 
PC Configuration tool in the OEM factories. 
(e)To show Master CFH (i) Alternate “CH” or 
“LL” or “Hdr” in numbers field with the actual 
temperature to indicate LL CH CFH. d. 
Configuration (1) Continue scrolling through set-
up screens until “Remote Firing Control” screen 
is reached. (2) Rmt On/Off selection chooses to 
navigate the user through the Master/Slave 
configuration as existing today (3) Set 
master/slave remote address as is done on 
currently on the local display. (4) The following 
parameters are mapped to Modbus addresses. 
LEAD LAG 
5 66—A1171 
(a) “LL” = LL Operation (3 
user selections available) (i) “Ldr” (i-a)Master 
Enable (i-b)Slave Enable (ii)“SLA” (ii-a)Slave 
Only Enable (ii-b)Master Disable (i) “OFF” (iii-
a)Master Disable (iii-b)Slave Disable (b)HS = 
On/Off Hysteresis (One value used for all LL 
boilers) (i) “HS” for on and off hysteresis values. 
(i-a)Only allow 1 setting for both on and off 
hysteresis values. (a-1)Must adhere to the 
strictest of either the HS On or Off limits. • 
Highest value of the “low” range limit in Sola 
control • Lowest value of the “high” range limit in 
Sola control (a-2)See Sola Modbus specification 
for details. • Typical values: 2-15 (c) BL = 
59