Bosch Appliances Home Security System D9412GV2 ユーザーズマニュアル
D9412GV2/D7412GV2 | Operation and Installation Guide | 8.0 On-Board Points
.
Bosch Security Systems, Inc. | 5/05 | F01U003641B
33
Figure 11: Wiring for Installation Using the Ademco AB-12 Bell/Housing
1 2 3 4 5 6
EARTH GROUND
COMMON
BATTERY NEGATIVE ONLY
Maximum Charging
Current 1.4 Amps.
BATTERY POSITIVE ONLY
RELAY A
RELAY B
RELAY C
+ AUX POWER
1
2
3
4
5
6
7
8
9
10
CLASS 2 TRANSFORMER
16.5 VAC 40 VA 60 Hz
Model D1640
Internally Fused - Do Not short
Requires Unswitched Outlet
Do Not Share With Other Equipment
16.5 VAC 40 VA 60 Hz
Model D1640
Internally Fused - Do Not short
Requires Unswitched Outlet
Do Not Share With Other Equipment
PROGRAMMABLE
ALARM OUTPUTS
ALARM OUTPUTS
Terminals
Requires Optional
Model D136 Relay
Model D136 Relay
In ALT ALARM
& SW AUX
&
7
8
GROUND FAULT DETECT
Enabled
Disabled
Disabled
VOLTAGE RANGES
Open 3.7 - 5.0 VDC
Normal 2.0 - 3.0 VDC
Short 0.0 - 1.3 VDC
Normal 2.0 - 3.0 VDC
Short 0.0 - 1.3 VDC
12
11
13
Point 1 Point 2
15
14
16
Point 3 Point 4
18
17
19
Point 5 Point 6
21
20
22
Point 7 Point 8
D9412GV2
TELCO
RING
TIP
PHONE LINE
SEIZED
SEIZED
PHONE
LED
LED
RED
ON when
communicating
OFF when idle
communicating
OFF when idle
PHONE LINE SEIZED
TIP
RING
TELCO CORD
MODEL D161
MODEL D161
1
2
4
3
5
1 - Bell
2 - Inner bell box lining
3 - Outer bell box
4 - Bell tampers
5 - 220 k
Ω
0.5 W EOL resistor (provided with the
Ademco AB-12 Bell/Housing)