2000 Series | Program Entry Guide | 3.0 
Reports 
EN | 12 
 
 
Bosch Security Systems | 7/05 | 35114F 
 
If the system is on with No Delay, alarm output at 
Terminals 4 and 5 follows the alarm delay 
programmed here. The alarm sounds at the keypad 
without delay. 
When mixing Delay Alarm points (Digit 2 set for 7 
or 8), with No Delay Alarm points (Digit 2 set for 5, 
6, or 9), the alarm output follows the programmed 
alarm delay if Delay Alarm points are faulted first. 
255 = Voice Verification:  Only set the 
Delay 
Alrm Rpt
 prompt to 255 when using an optional 
two-way voice verification module. When the 
Delay 
Alrm Rpt
 prompt is set to 255, an Alarm event on a 
point with 2, 3, 7, or 8 in Digit 2 sends an Alarm 
Report and begins the two-way voice verification 
process. Do not set the 
 Delay Alrm Rpt
 prompt to 
255 if a voice verification module is not connected to 
the control panel, because unexpected control panel 
operation results. 
 
 
Duress Reports and A, B, C Key Reports 
are affected by Alarm Report Delay. These 
reports are sent immediately in all cases. 
 
 
 
The Security Industry Association (SIA) 
recommends the Delay Alarm Report 
feature be enabled with the delay set to 15 
seconds. Enter 15 at this prompt to comply 
with the SIA recommendation. 
Press the [0] key to disable the 
Delay Alrm Rpt
 
prompt for all points. 
5 Cancel Rpt 
Default: 
Yes
 
Selection: 
Yes, No
 
0 No 
1 Yes 
Set the 
Cancel Rpt
 prompt to Yes to enable Cancel 
Report. If a user turns the system off after an alarm, 
but before bell time expires, a Cancel
 
Report follows 
the Alarm Report. 
If the user turns the system off before 
Delay Alrm 
Rpt
 prompt time expires, the control panel sends no 
Alarm, Cancel, or Restoral Report for points 
programmed with a 2, 3, 7, or 8 in Digit 2 of the 
point code. 
If you set the 
Cancel Rpt
 prompt to No, the control 
panel does not send Cancel Reports. 
6 Restoral Rpts 
Default: 
No
 
Selection: 
No, Yes, Delay
 
0 No 
1 Yes 
2 Delay 
Set the 
Restoral Rpts
 prompt to Yes to send 
Restoral Reports to the receiver for 
all points. The 
system sends Restoral Reports when points return to 
normal (not faulted) after an Alarm or Trouble 
Report. 
Set the 
Restoral Rpts
 prompt to No to prevent the 
system from sending Restoral Reports for any point. 
Set the 
Restoral Rpts
 prompt to Delay to delay 
sending Restoral Reports until bell time expires.  
7 AC Fail Buzz/Rpt 
Default: 
No Buzz, No Report
 
Selection: 
No Buzz, No Report 
Buzz, No Report 
Buzz, Report 
Buzz, Tag-Along Rpt 
No Buzz, Report 
No Buzz, Tag-Along Rpt
 
No Buzz No Report 
Buzz, No Report 
Buzz, Report 
Buzz, Tag-Along Rpt 
No Buzz Report 
No Buzz, Tag-Along Rpt 
The control panel monitors AC power. When AC 
power to terminals 1 and 2 is interrupted, the control 
panel waits 60 seconds. If AC power is not restored 
within 60 seconds, it provides the response 
programmed in 
AC Fail Buzz/Rpt
When set to 
No Buzz, No Report the system only 
flashes the OK light at the keypad to indicate a 
system trouble. It does not sound the trouble tone or 
send a report to the receiver. 
When set to 
Buzz, No Report the system flashes the 
OK light at the keypad to indicate a system trouble 
and sounds the trouble tone. No report is sent to the 
receiver.