Bosch 2000 ユーザーズマニュアル

ページ / 72
2000 Series | Program Entry Guide | 11.0 
Point Codes 
EN | 47 
 
Bosch Security Systems | 7/05 | 35114F 
 
Table 9: Digit Selection Summary 
 
Selection
 
Digit 1 
Point Type 
Digit 2  
Alarm Response 
Digit 3 
Point Options 
Digit 4 
Device Address 
Digit 5 
Sensor Loop 
Disabled 
Set to 0 for RF 
keypad. 
No reports, No Swinger, 
No Output  
Set to 0 for  RF keypad. 
No Troubles, Not Cross Point,  
Not Partner Point  
Set Digit 3 to 0 for RF keypad. 
On-Board 
 
Fire 
Reports, No Report 
Delay, No Swinger, No 
Output 
Trouble Open, No Trouble 
Short, No Double Knock, No 
Cross Point, No Partner Point.  
Device  
Address 1 
 
Fire with Alarm 
Verify (use with 
Point 1 only) 
Reports, Report Delay, 
No Swinger, No Output 
No Trouble Open, Trouble 
Short, No Double Knock, No 
Cross Point, No Partner Point.  
Device  
Address 2 
 
Buzz on Fault 
Reports, Report Delay, 
Swinger, No Output 
Trouble Open, Trouble Short, 
No Double Knock, No Cross 
Point, No Partner Point. 
Device  
Address 3 
 
24-hour, Visible 
Reports, No Report 
Delay, Swinger, No 
Output 
No Trouble Open, No Trouble 
Short, Double Knock, No Cross 
Point, No Partner Point.  
Device  
Address 4 
 
24-hour, Invisible 
No Reports, No Report 
Delay, No Swinger, 
Output 
Trouble Open, No Trouble 
Short, Double Knock, No Cross 
Point, No Partner Point.  
Device  
Address 5 
 
Controlled, All, Delay 
Reports, No Report 
Delay, No Swinger, 
Output 
No Trouble Open, Trouble 
Short, Double Knock, No Cross 
Point, No Partner Point. 
Device  
Address 6 
 
Controlled, All No 
Delay 
Reports, Report Delay, 
No Swinger, Output 
Trouble Open, Trouble Short, 
Double Knock, No Cross Point, 
No Partner Point 
Device  
Address 7 
 
Controlled, Part, 
Delay 
Reports, Report Delay, 
Swinger, Output 
No Trouble Open, No Trouble 
Short, No Double Knock, Cross 
Point, No Partner Point. 
Device  
Address 8 
 
Controlled, Part, No 
Delay 
Reports, No Report 
Delay, Swinger, Output 
Trouble Open, No Trouble 
Short, No Double Knock, Cross 
Point, No Partner Point. 
 
 
Keyswitch 
 
No Trouble Open, Trouble 
Short, No Double Knock, Cross 
Point, No Partner Point. 
 
Extended  Delay, All 
 
Trouble Open, Trouble Short, 
No Double Knock, Cross Point,  
No Partner Point 
 B 
Extended Delay, Part 
 
No Trouble Open, No Trouble 
Short, No Double Knock, No 
Cross Point, Partner Point. 
 
 
 
Trouble Open, No Trouble 
Short, No Double Knock, No 
Cross Point, Partner Point. 
 D 
 
 
No Trouble Open, Trouble 
Short, No Double Knock, No 
Cross Point, Partner Point. 
 
 
 
Trouble Open, Trouble Short, 
No Double Knock, No Cross 
Point, Partner Point. 
 F 
G to P 
 
 
 
 
G to P