Table 18: Relay Function Selections 
 
Programmers Keypad 
Description 
No Output 
No output at the relay terminal. 
Alarm 
Provides a steady output when a point is in an alarm condition.  
The relay output follows Bell Time.  
Note: 
This output does not occur for alarms caused by A, B, C Keys. 
Entering a combination to acknowledge an alarm resets the relay. 
Select the points to monitor for alarms at the Parameter prompt. 
Alarm Memory 
Provides a steady output when a point shows alarm memory at the keypad. 
Turning the system on clears alarm memory and ends the output. This output 
does not occur for alarms caused by A, B, C Keys. 
Select the points to monitor for alarm memory at the Parameter prompt. 
Point Trouble 
Provides a steady output when selected points are in trouble.  
Select the points to monitor for troubles at the Parameter promptSwinger 
bypass is a point trouble and activates the Point Trouble Relay function. 
Follow Point 
Provides a steady output when selected points are faulted (including point trouble 
and alarm). 
Select the points to monitor for faults at the Parameter prompt. 
Watch Tone 
Activates the relay output in parallel to the watch tone for selected points. Refer to 
Key 7, Watch Tone in the User’s Guide. If you set the watch tone to No Tone, the 
Watch Tone relay does not activate. Select the points for Watch Tone monitor at 
the Parameter prompt. 
A,B,C Key, Steady 
Activates the relay output when a user presses a selected function key. The relay 
output remains activated until a user performs a System Reset (presses [3] and 
enters a passcode). 
Select the function keys to monitor at the Parameter prompt. 
A,B,C Key, Pulse 
Activates the relay output when a user presses a selected function key. The relay 
output pulses until a user performs a System Reset (presses [3] and enters a 
passcode). 