Weil-McLain NX ユーザーズマニュアル

ページ / 20
WM  550-141-996/1105
 
  
Page 7
RWB 6104WMNX R1005
Inspect/Prepare Installation Site
Clearances to Burner and Appliance
  Provide space around burner and appliance for 
ease of service and maintenance.
  Check the minimum clearances against those 
shown by the appliance manufacturer and by ap-
plicable building codes.
Inspect Chimney or Direct Vent System
  Inspect the chimney or vent. Make sure it is prop-
erly sized and in good working condition. Follow 
the instructions supplied by the appliance manu-
facturer.
Combustion Air Supply Information
Warning–Adequate Air 
Supply Required 
The burner cannot properly burn the fuel if it is 
not supplied with a reliable combustion air 
source. A non-reliable air source could result in 
incomplete combustion, causing sooting and 
possible carbon monoxide emission.  
Possible Sooting & 
Asphyxiation Hazard
S104
!
one near the bottom of the enclosure. Each open-
ing must have a free area of not less than one (1) 
square inch per 1,000 BTU’s per hour of the total 
input rating of all appliances within the enclosure. 
The openings should have free access to the build-
ing interior, which should have adequate infi ltration 
from the outside.
  Exhaust fans and other air-using devices: Size 
air openings large enough to supply all air-using 
devices in addition to the minimum size required 
for combustion air. If there is any possibility of the 
equipment room developing a negative pressure 
due to exhaust fans, clothes dryers, etc., either 
pipe combustion air directly to the burner or provide 
a sealed enclosure for the burner and supply it with 
its own combustion air supply.
Safety Shutoff for Direct Vent System
  The direct vent blocked fl ue safety shut off system, 
refer to Figure 2,  shuts down the burner if the ex-
haust fl ue is blocked and/or if the air inlet is blocked.  
It recognizes a blocked fl ue by sensing excessive 
pressure in the combustion chamber.  It recognizes 
a blocked inlet by sensing excessive vacuum in the 
air inlet adapter.
  This system meets the requirements for a blocked 
fl ue or blocked combustion air inlet per CSA Stan-
dard B140.0.  It is designed to interrupt the cad cell 
circuit and allow the control to shut down the burn-
er. 
Direct/Sidewall Venting Application 
  For direct vent installations, follow instructions pro-
vided with appliance and direct vent system.  Out-
side combustion air is required for direct venting.
Site Preparation
SK9803A
Figure 2. Pressure Switch Installation
  See NFPA Standard 31 for complete details.
  Appliances located in confi ned  spaces:  All 
confi ned spaces should have two (2) permanent 
openings; one near the top of the enclosure and