Analog Input
A/D Converter: One per point
Channels: 16
Resolution: 24-bit
Current and Voltage: 0-20 mA, 0-5 V/1-5 V/±5 V/±10 V,
0.1% accuracy over full operating temperature range.
Thermocouple: 0.2% accuracy over full operating temperature
range.
RTD: Pt100/Cu50, 0.2% accuracy over full operating temp.
range (2- or 3-wire)
Isolation: Point, 500 VAC between any two channels,
and between input and ground
Analog Output
D/A Converter: One per point
Channels: 8
Resolution: 12 bit
Signal: 0-20 mA, 0-10 V, 0.2% accuracy over full operating
temp. range.
Isolation: Point, 500 VAC between any two channels,
and between output and ground
Digital Input
Channels: 16
Signal: 24 V, positive/negative (sink/source) logic, 1 ms SOE
Isolation: Group, 1000 VAC between groups, 500 VAC between
input and field grounds
Communications
Redundant 100 MB Ethernet with IEEE1588, twisted pair or fiber
optic, up to 2 kilometers
Power Requirements
Power Supply Voltage Range: 90-240 VAC, 50/60 Hz
or 110/220 VDC
Redundancy: 1:1 redundancy optional
Power Consumption and Heat Dissipation
Codes and Standards
Safety: IEC61508, UL508
Communications: IONET EGD
EMC:
I/O Type
Power
Consumption (W)
Heat
Dissipation (W)
AI mAV
17.65
4.47
AI RTDTC
6.45
2.5
AO
9.65
3.06
DI 16 channel (24 V)
3.57
3.57
DO relay (220 VAC)
11.25
11.25
IEC61000-4-2
IEC61000-4-3
IEC61000-4-4
IEC61000-4-5
IEC61000-4-6
IEC61000-4-8
IEC61000-4-9
IEC61000-4-10
IEC61000-4-12
TC Type
Range Voltage mV
Range °C
T
-5.603 to 17.818
-200 to 350
J
-7.890 to 69.553
-200 to 1200
E
-8.825 to 76.373
-200 to 1000
K
-5.891 to 52.410
-200 to 1300
N
-3.990 to 47.513
-200 to 1300
B
0.787 to 11.263
400 to 1600
R
0 to 18.884
0 to 1600
S
0 to 17.947
0 to 1700