Vogelzang International NORSEMANTM SOlid FuEl WARM AiR FuRNAcE 2500 ユーザーズマニュアル

ページ / 28
VGZ-018 / 0805.1 
NORSEMAN™ 1500/2500 FuRNAcE / 
Page 
chiMNEY coNNEctioNs continued …
coNNEctoR pipE iNstAllAtioN
1.  The crimped end of the connector pipe fits inside 
the furnace flue collar. Install additional pipe and 
elbow with the crimped end towards the furnace. 
This will allow any condensation in the flue to run 
back into the firebox.
2.  Horizontal  pipe  runs  must  slope  upwards  
towards the chimney at least 1/4˝ per foot of hori-
zontal run.
3.  You  must  have  at  least  18  inches  of  clearance 
between any horizontal piping and the ceiling.
4.  connector pipe cannot extend into the chimney flue 
(figure 14).
5.  Secure  pipe/elbow  sections  with  three  (3)  sheet 
metal  screws  at  each  joint  to  make  the  piping 
rigid.
Fig. 14 – Stovepipe/Flue Connections
 
 
CORRECT 
wRONg 
wRONg
NOTE: CONNECTOR PIPE IS Not iNclUDED
TO  PURChASE, vISIT YOUR  LOCAL  hARD-
wARE,  hOmE  OR  BUILDINg  CENTER.  SEE   
“LOCATINg  FURNACE”  PAgE  6  FOR  ADDI-
TIONAL SPECIFICATIONS.
The chimney used for a furnace must not be used to 
ventilate the cellar or basement. If there is a clean out 
in the base of the chimney, close it tightly.
ChImNEY
FLUE
5/8" TILE
ChImNEY
LINER
mASONRY
ChImNEY
ThImBLE
COLLAR
6˝ ROUND
24 ga. BLACk
CONNECTOR
STOvEPIPE
8˝ mIN.
LINER
BELOw
ENTRY
hOLE
Fig. 12 - Masonry Chimney Connection
If you have any questions regarding venting your 
furnace, contact the manufacturer or contact the Na-
tional Fire Protection Association (NFPA) and request 
a copy of the latest editions of NFPA Standard 211 
and NFPA Standard 908. Their address is:
 Battery March Park, Quincy, MA 02269.
Fig. 13 - Chimney Construction 
Through Roof
continued on next page