Utica Boilers UB95M-200 インストール手順

ページ / 28
10
6 - CHECKOUT PROCEDURES AND ADJUSTMENTS
Figure 2  Multimeter
8. 
Drill ½” hole in plastic CPVC vent pipe or exhaust 
tee, just large enough to allow access for combustion 
analyzer sample probe.
9. 
Turn thermostat to closed position so appliance is 
activated.
10. 
Set appliance to high fire mode as described in “User 
Interface Quick Reference” section 10 page 21  and 
allow it to run for approximately 5 minutes.
11. 
Insert sample probe of your combustion analyzer into 
drilled hole from Step 8. Insert about halfway into 
exhaust gas stream. Take flue gas reading and observe 
% CO
2
 and CO values.  Adjust throttle screw until 
correct readings are reached. 
12. 
Turning throttle screw clockwise decreases rate and 
CO
2
 value. Turning throttle screw counter clockwise 
increases rate and CO
2  
value. 
13. 
Allow appliance to stabilize for one minute after 
adjusting throttle screw before you take reading with 
combustion analyzer.
NOTICE
CO levels should not exceed 80 ppm.
14. 
Set appliance to low fire mode as described in “User 
Interface Quick Reference” section. Check CO
2
 level as 
stated in Step 5. Low fire and high fire values should be 
approximately same.
15. 
After adjustments are made stop appliance. Disconnect 
pressure gauge, tighten inlet pressure tap on gas valve, 
remove CO
2
 meter from CPVC pipe, and seal hole with 
¼” NPT black iron plug. Use thread sealing compound 
or teflon tape to ensure proper seal.
16. 
Return thermostat switch to its original position.
Measure Natural Gas Input Rate
1. 
Correct input rate is essential for proper and efficient 
operation of burner and boiler.
2. 
Determine elevation at installation site.
3. 
See “Installation, Operation and Maintenance Manual” 
to determine correct approximate input rate for local 
elevation.
4. 
Obtain yearly average heating value of local gas utility. 
At sea level elevation, it should be about 1000 BTU per 
standard cubic foot.
5. 
Operate boiler for 5 minutes.
6. 
Turn off all other gas appliances, extinguishing standing 
pilots where applicable.
7. 
At gas meter, measure time in seconds required to use 
one cubic foot of gas.
8. 
Boiler must be in high fire mode for this operation. See 
“User Interface Quick Reference” section 10, for more 
information on placing boiler in high fire mode. 
Calculate BTUH Input Rate as follows:
Btuh input rate =
3600 x heating value from Step 4
time in seconds
9. 
Measured input rate varies with vent length, gas 
calorific content, altitude and ambient temperature. 
Set boiler with combustion specifications in “Boiler 
Adjustment” section 6 page 9.
Determine Lp Gas Input Rate
Determine LP gas input rate by measuring C0
2
 produced 
during combustion. Set this value according to guidelines 
table on page 11.
Measure Flame Sense
Flame sense can be indicator of issues with air intake 
venting, exhaust venting, burner and ignitor condition and 
supply gas piping pressure. 
Use multi meter capable of reading 0-20 VDC. 
Attach one lead to “F” terminal on low voltage terminal 
block on boiler control. 
Attach other lead to any ground surface on boiler. See 
Figure 2. 
Flame sense voltage shall be in accordance with values 
listed in Flame Signal Guidelines chart page 11.