.  8 single-ended 4-20 mA output channels 
.  Non-incendive field circuits 
.  HART pass-through 
.  HART variable and status reporting 
.  Valve positioners and remote indicators, etc.  
.  Open circuit detection on each channel 
.  24 V dc bussed field power required 
Module Specifications 
Inputs 
Number of channels ...............................................8, single-ended
Nominal signal range (span) ..........................................4 to 20 mA
Full signal range.................................................................1 to 23 mA
Open loop detection threshold ...............................0.7 ± 0.25 mA
Output compliance ..............................20 mA at 21.6 V dc supply
....................................................................................(into 700 Ω load)
Accuracy (over temp range) .................................± 0.25% of span
Resolution ..................................................................................12 bits
Isolation
     (any channel to Railbus) .................................................100 V ac
     (between channels)................................................................none
Configurable Parameters
Initialization state..................................................predefined value
Drive on fail-safe ................................predefined value/last value
Channel status.......................................................... active /inactive
HART variable and status reporting.....................enable /disable
NT
-8102-HO-IP
Image Description
8 Channel Analog Output
4–20 mA with HART® 
Response Time
Signal change to availability on Railbus 
     4–20 mA mode .........................................................25 ms (max.)
     HART mode......................................................0.75 s per channel
Safety
FM non-incendive field wiring parameters (each channel) 
..................V
oc
 = 28.7 V; I
sc
 = 33 mA; C
a
 = 0.17 µF; L
a
 = 11.0 mH
Power Supplies
Railbus (12V) current ..................................................100 mA (typ.)
.........................................................................................150 mA (max.)
Bussed Field Power .................... 300 mA (max.) at 24 Vdc ± 10%
Mechanical
Module Key Code .............................................................................A4
Module width ............................................................................42 mm
Weight............................................................................................200 g
 
Field Terminals 
Field Wiring
Recommended 
Field Terminal
Compatible 
Field Terminal
General Purpose
NT-8602-FT-ST 
Standard
NT-8604-FT-FU 
Fused
Class 1, Div 2 
or Zone 2 hazard-
ous area
NT-8601-FT-NI 
Non-incendive 
NT-8603-FT-FU 
Non-incendive 
NovaTech 8000 Series I/O Family
3AFE
OR
-58
M0
2EGULATOR
/THER
CHANNELS
2AILBUS

"USSED
$!
#HANNEL
 M!
0
)
((#
Copyright © 2007 NovaTech, LLC. All rights reserved. All trademarks 
are properties of their respective owners. NovaTech is a registered 
trademark  of  NovaTech,  LLC.  The  information  in  this  literature  is 
subject to change without notice and is not to be construed as a 
warranty.  DS_8102_0607