APOGEE Unit Vent Controller
0 to 10 V Output Owner’s Manual 
8  
 
Siemens Building Technologies. Inc. 
Cooling Loop – maintains room temperature setpoint by turning valves on and off and using 
free cooling (mixed air control) when available. 
Auxiliary Loop – modulates the auxiliary loop using the auxiliary setpoint and discharge 
setpoint (2284). 
Mixed Air Loop – modulates the mixed air loop using the mixed air setpoint and mixed air 
temperature (2283). 
DX Loop – modulates the cooling loop using the control setpoint and room temperature 
(2284).  
Morning Warm-up/Cool-down 
Morning warm-up or cool-down occurs after the controller switches from night mode to day 
mode, upon power-up, or if the controller is reset. During morning warm-up or cool-down, the 
controller provides maximum heating or cooling with the outdoor air damper closed until the 
temperature of the space reaches setpoint. 
ON/OFF Coil Valve Control 
When a face-bypass configuration is used, the coils may be turned on and off with two-
position valves using DOs. 
Electric Heat 
If electric heat is used, it is controlled as follows:  
HTG OUTPUT 
(Point 60) 
Stage 1 
Stage 2 
Stage 3 
0% to 33% 
ON 
OFF 
OFF 
34% to 66% 
ON 
ON 
OFF 
67% to 100% 
ON 
ON 
ON 
In addition, no stage may turn on or off until the time delay has elapsed. Stage one will 
always be the first stage to turn on and the last stage to turn off. 
Fan Operation 
Day Mode – The fan is on all the time. 
Night Mode – The fan only operates when required for heating or cooling. 
Fail-safe Operation 
A low temperature detection thermostat (LTDT) can be used to signal the controller when the 
temperature drops below the low temperature limit.